2 Equipment Description
2.27 EUCN Cable System
R688 HPM High-Performance Process Manager Service 145
December 2020 Honeywell
FTE cable B on an ENIM
have a problem
Redundant ENIM:
ATTENTION
A disjoined node (for example, a double FTE cable fault) will still be shown in the “FAIL”
(meaning X X X X) state on the $FTESTS2 schematic, but will no longer contribute to the
overall composite FTE community status.
Note: The RESET STATS target can still be used to remove the indication of disjoined nodes.
LCN system alarm can also be caused by a switch uplink failure (for example, CF9), check your
upper-level network topology to confirm this.