Table 58 Communications and Control Processor Hard Failure Codes 
Corrective Action 
(See Table 57) 
Collector task did not correctly 
schedule a timed resetting of 
timesynch timer LEF. 
MTOS error, could not set LEF of 
Event Distributor task. 
MTOS error, could not resume Event 
Distributor task. 
Resource error on UM$SEND_IOL call 
that initiates collection of given SIOM 
ECL. 
Collector task could not reset its own 
LEF. 
Collector task did not correctly 
schedule a timed resetting of its own 
LEF. 
Collector task did not correctly wait for 
setting of its own LEF. 
Could not raise Event Collector task's 
priority to that above IOL l/F task. 
Did not receive a resume from IOL l/F 
task in 30 seconds for completion of 
collection on at least one IOM ECL. 
Could not return Event Collector task 
to its inherent priority. 
Resource error on UM$SEND_IOL call 
for collection of SIOM ECL summary 
bytes. 
Illogical condition, could not find 
corresponding collection status 
connection record. 
Invalid SIOM Point/System bracket 
event 
Invalid SIOM Recovery bracket event 
Invalid PROCESS ALARM event from 
AIM module 
Invalid SIOM STATE CHANGE event 
Resource error on UM$SEND_IOL call 
for update of SIOM ECL remove 
pointer