A cable with an incorrectly attached lug can damage the packet transport
switch.
Figure 87: Grounding Cable Lug
g006590
Crimp area
All measurements in inches
0.38
2 holes
2.57
0.32 0.380.63
0.76
End view
0.12
You must supply a grounding cable. Table 45 on page 260 summarizes the specifications
for the grounding cable and lug.
In addition, GR1089-CORE requires the following:
The grounding conductor must be copper.
Bare conductors shall be coated with an antioxidant before crimp connections are
made.
Plated areas that are electrically connected to the grounding conductor shall be cleaned
and free of contaminants before the connection is made.
Table 45: Grounding Cable Specifications
0-AWG (53 mm
2
),
Cable Specification
Cable lug; dual hole, sized to fit 1/4-20 UNC terminal studs at
15.86-mm (0.625-in.) center line.
Connector Specification
Related
Documentation
PTX5000 Chassis Description on page 12
Tools and Parts Required to Ground the PTX5000 Packet Transport Switch on page 83
Connecting the PTX5000 Grounding Cable on page 83
PTX5000 DC Power System Electrical Specifications
Table 46 on page 260 lists the DC power system electrical specifications.
Table 46: Power System Electrical Specifications
SpecificationItem
Operating range: –40.0 to 72.0 VDCDC input voltage