Installing the Open-Frame Rack Mounting Shelf
Before mounting the chassis in an open-frame rack, you must first install the open-frame
rack mounting shelf.
To install the open-frame rack mounting shelf (see Figure 34 on page 73):
1. On the rear of each rack rail, partially insert a mounting screw into the highest hole
specified in Table 28 on page 72 for the open-frame rack mounting shelf.
2. Install the open-frame rack mounting shelf on the rack. Hang the shelf over the
mounting screws using the keyhole slots located near the top of the shelf flanges.
3. Partially insert screws into the open holes in the flanges of the open-frame rack
mounting shelf.
4. Tighten all the screws completely.
Figure 34: Installing the Mounting Hardware for an Open-Frame Rack
g006188
73Copyright © 2012, Juniper Networks, Inc.
Chapter 7: Installing the PTX5000 Packet Transport Switch Mounting Hardware