11.3.6 Motor potenometer setpoint source
The "Mot
or potenometer" funcon can be used as an alternave setpoint control that is
controlled via two funcons: "Motor potenometer up" and "Motor potenometer down".
The "Setpoint = Motor potenometer" funcon enables a setpoint change-over to the motor
potenometer.
Precondions
A setpoint change-over to the motor potenometer is only eected if
no setpoint source with a higher priority has been selected. 4Priority of the setpoint sour-
ces^ 193
no jog operaon is acve ("Foward jog (CW)" and "Backward jog (CCW)" funcons).
Details
If the motor potenometer is acve as setpoint source, the setpoint generated by this func-
on ("MOP value") can be changed according to the truth table via the triggers assigned to
the two "Motor potenometer up" and "Motor potenometer down" funcons:
Motor potenometer
up
Motor potenometer
down
R
esponse of the funcon
FALSE FALSE Last MOP value is maintained.
TRUE FALSE MOP value is increased to a maximum of the upper range limit with acceleraon me 2.
FALSE TRUE MOP value is decreased to a maximum of the lower range limit with deceleraon me 2.
TRUE TRUE Last MOP value is maintained.
Starng performance
In the default seng, the last MOP value is used as inial v
alue. As an alternave, an adjust-
able inial value or the minimum value can be used for starng. The starng performance
can be selected in 0x4003 (PAR 413).
The last MOP v
alue is sll provided aer switching the mains voltage o and on again.
Range limits, acceleraon mes, and deceleraon mes
Parameter Speed mode Process controller mode
Lower range limit Minimum frequency
0x2915 (PAR 210)
Setpoint limits (process c
ontroller): Minimum
setpoint
0x404E:001 (PAR 605/001)
Upper range limit Maximum frequency
0x2916 (PAR 211)
Setpoint limits (process controller): Maximum
setpoint
0x404E:002 (PAR 605/002)
Acceleraon me Acceleraon me 2
0x2919 (PAR 222)
Setpoint ramp (process controller)
0x404B (PAR 604)
Deceleraon me Deceleraon me 2
0x291A (PAR 223)
Setpoint ramp (process controller)
0x404B (PAR 604)
Parameter Name / value range / [default seng] Info
0x2631:023
(PAR 400/023)
Funcon assignment: Motor potenometer up
(Funcon lis
t: MOP up)
For possible sengs see descripon for
0x2631:001 (PAR 400/001). ^ 188
Assignment of a trigger for the "Motor potenometer up" funcon.
Trigger = TRUE: setpoint generated by the "Motor potenometer" func-
on ("MOP value") is maximally increased to the upper range limit with
acceleraon me 2.
Trigger = FALSE: last MOP value is maintained.
Notes:
If the "Motor potenometer up" and "Motor potenometer down"
funcons are acve at the same me, the last MOP value is main-
tained.
Acceleraon me 2 can be set in 0x2919 (PAR 222).
00 Not connected No trigger assigned (trigger is constantly FALSE).
Flexible I/O conguraon
Setpoint change-over
Motor potenometer setpoint source
198
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.actechdrives.com - Email: info@actechdrives.com

Table of Contents

Other manuals for Lenze i510

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i510 and is the answer not in the manual?

Lenze i510 Specifications

General IconGeneral
Product CategoryDC Drives
Seriesi510
Protection ClassIP20
CommunicationCANopen, Modbus RTU
Protection FeaturesOvervoltage, Undervoltage
Operating Temperature-10 to +50 °C
Storage Temperature-25 to +70 °C
Humidity5% to 95% (non-condensing)
Control ModeV/f control

Related product manuals