12 Technical data
12.1 Standards and operang condions
Conformies
CE 2014/35/EU Low-Voltage Direcve
2014/30/EU EMC Direcve (reference: CE-typical drive system)
EAC TR TC 004/2011 Eurasian conformity: Safety of low voltage equipment
TP TC 020/2011 Eurasian conformity: Electromagnec compability of technical
means
RoHS 2 2011/65/EU Restricons for the use of specic hazardous materials in electric
and electronic devices
Approvals
UL UL 61800-5-1 for USA and Canada (requirements of CSA 22.2 No. 274)
Energy eciency
Class IE2 EN 50598-2
Type of protecon
IP20 EN 60529
Type 1 NEMA 250 Protecon against contact
Open type only for UL approved systems
Insulaon resistance
Overvoltage category III EN 61800-5-1 0 … 2000 m a.m.s.l.
Overvoltage category II above 2000 m a.m.s.l.
Control circuit isolaon
Safe mains isolaon by double/reinforced
insulaon
EN 61800-5-1
Protecve measures against
Short circuit
Earth fault Earth fault strength depends on the operang status
Overvoltage
Motor stalling
Motor overtemperature I²xt monitoring
Leakage current
> 3.5 mA AC, > 10 mA DC EN 61800-5-1 Observe regulaons and safety instrucons!
Mains switching
3-me mains switching in 1 min cyclic, without restricons
Starng current
≤ 3 x rated mains current
Mains systems
TT Voltage to earth/ground: max. 300 V
TN
IT Apply the measures described for IT systems!
IT systems not relevant for UL approved systems
Operaon on public supply systems
Implement measures to limit the radio
interference t
o be expected:
The compliance with the requirements for the machine/plant is
the responsibility of the manufacturer of the machine or plant!
< 0.5 kW: with mains choke EN 61000-3-2
0.5 ... 1 kW: With acve lter
> 1 kW at mains current ≤ 16 A: without
addional measures
Mains current > 16 A: with mains choke or
mains lter, with dimensioning for rated
power. Rsce ≥ 120 is to be met.
EN 61000-3-12 RSCE: Short-circuit power rao at the connecon point of the
machine/plant to the public network.
Requirements to the shielded motor cable
Capacitance per unit length
C-core-core/C-core-shield < 75/150 pF/m ≤ 2,5 mm² / AWG 14
C-core-core/C-core-shield < 150/300 pF/m ≥ 4 mm² / AWG 12
Electric strength
Technical data
Standards and operang condions
223