Parameter Name / value range / [default seng] Info
0x2D84:002 Heatsink temperature monitoring: Warning threshold
50.0 ... [80.0]* ... 100.0 °C
Default seng depending on the size.
W
arning threshold for temperature monitoring.
If the heatsink temperature exceeds the threshold set here, the inver-
ter outputs a warning.
The warning is reset with a hysteresis of approx. 5 °C.
If the heatsink temperature increases further and exceeds the non-
adjustable error threshold (100 °C), ), the inverter changes to the
"Fault" device status. Further operaon of the inverter is disabled by
controller inhibit.
5.3.1 Logbook
For diagnosc purposes, the logbook contains the last 32 error messages and warning signals
of the inverter, which ha
ve occurred during operaon.
Precondions
The logbook can only be accessed
via the user interface of »EASY Starter« ("Diagnoscs" tab) or
via network.
Details
In contrast to the error history buer, the logbook addionally protocols the following events:
Fault messages
Change-over from normal to setup mode (and vice versa)
Execuon of device commands
Avoidance of safety funcons
The logbook entries are saved persistently in the inverter. If all 32 memory units are occupied,
the oldest entry is deleted for a new entry. By means of the "Delete logbook" device com-
mand, all logbook entries can be deleted.
Accessing the logbook with »EASY Starter«
1.Select the inverter on the le side in the »EASY Starter« device list.
2.Change to the "Diagnoscs" tab.
3.Click the
icon to open the logbook.
Observe that the logbook only presents a snapshot at the me the data are read out. If a new
event occurs, the logbook mus
t be read out again so that the new event becomes visible.
Accessing the logbook via network
The logbook can also be accessed via network from a higher-level controller or a visualisaon.
The structure of the diagnosc messages complies with the "ETG.1020" standard of the Ether-
CAT Technology Group (ETG).
See chapter 13.3 of document "ETG.1020 Protocol Enhancements" provided by
the EtherCAT Technology Group (ET
G) for detailed informaon on the structure
of the diagnosc messages.
Parameter Name / value range / [default seng] Info
0x2022:015
(PAR 700/015)
Device commands: Delet
e logbook
(Device commands: Delete logbook)
0 ... [0] ... 1
Seng can only be changed if controller inhibit is
acve.
1 = delete all entries in the logbook.
Diagnoscs and fault eliminaon
Diagnoscs
Logbook
45