7.6 Switching frequency changeover
The switching frequency of the inverter has an impact on the smooth running performance
and the noise generaon in the motor connected as well as on the power loss in the inverter.
The lower the switching fr
equency, the beer the concentricity factor, the smaller the power
loss and the higher the noise generaon.
Parameter Name / value range / [default seng] Info
0x2939
(PAR 305)
Switching frequency
(S
witching frequency)
•
Seng can only be changed if controller inhibit is
acve.
Selecon of the inverter switching frequency.
Abbreviaons used:
•
"Variable": adaptaon of the switching frequency as a funcon of the
current
•
"Drive-opt.": drive-opmised modulaon ("sine/delta modulaon")
•
"Fixed": xed switching frequency
•
"Min. Pv": addional reducon of power loss
1 4 kHz variable / drive-opmised
2 8 kHz variable / drive-opmised
3 16 kHz variable / drive-opmised
5 2 kHz xed / drive-opmised
6 4 kHz xed / drive-opmised
7 8 kHz xed / drive-opmised
8 16 kHz xed / drive-opmised
11 4 kHz variable / min. Pv
12 8 kHz variable / min. Pv
13 16 kHz variable / min. Pv
15 2 kHz constant/min. Pv
16 4 kHz constant/min. Pv
17 8 kHz constant/min. Pv
18 16 kHz constant/min. Pv
21 8 kHz variable / drive-opmised / 4 kHz
min.
22 16 kHz variable / drive-opmised / 4 kHz
min.
23 16 kHz variable / drive-opmised / 8 kHz
min.
31 8 kHz variable /min. Pv / 4 kHz min.
32 16 kHz variable /min. Pv / 4 kHz min.
33 16 kHz variable /min. Pv / 8 kHz min.