11.7 Acvang ramp 2 manually
The "Acvate ramp 2" funcon serves to manually acvate acceleraon me 2 and deceler
a-
on me 2.
Parameter Name / value range / [default seng] Info
0x2631:039
(PAR 400/039)
Funcon assignment: Acvate ramp 2
(
Funcon list: Acv. ramp 2)
For possible sengs see descripon for
0x2631:001 (PAR 400/001). ^ 188
Assignment of a trigger for the "Acvate ramp 2" funcon.
Trigger = TRUE: acvate acceleraon me 2 and deceleraon me 2
manually.
Trigger = FALSE: no acon / deacvate funcon again.
Notes:
Acceleraon me 2 and deceleraon me 2 are also acve if the
"Motor potenometer" funcon is acve or the frequency setpoint
(absolute value) > auto-changeover threshold 0x291B (PAR 224).
Acceleraon me 2 can be set in 0x2919 (PAR 222).
Deceleraon me 2 can be set in 0x291A (PAR 223).
00 Not connected No trigger assigned (trigger is constantly FALSE).
0x2917
(PAR 220)
Acceleraon me 1
(Acceleraon me 1)
0.0 ... [5.0] ... 3600.0 s
The acceleraon me set refers to the acceleraon from standsll to the
maximum frequency set. In the case of a lower setpoint selecon, the
actual acceleraon me is reduced accordingly.
0x2918
(PAR 221)
Deceleraon me 1
(Deceleraon me 1)
0.0 ... [5.0] ... 3600.0 s
The deceleraon me set refers to the deceleraon from the maximum
frequency set to standsll. In the case of a lower actual frequency, the
actual deceleraon me is reduced accordingly.
0x2919
(PAR 222)
Acceleraon me 2
(Acceleraon me 2)
0.0 ... [5.0] ... 3600.0 s
The acceleraon me set refers to the acceleraon from standsll to the
maximum frequency set. In the case of a lower setpoint selecon, the
actual acceleraon me is reduced accordingly.
Acceleraon me 2 is acve if
"Motor potenometer" funcon is acve, or
frequency setpoint (absolute value) > auto-change-over threshold
0x291B (PAR 224), or
the trigger assigned in 0x2631:039 (PAR 400/039) of the "Acvate
ramp 2" funcon is TRUE.
0x291A
(PAR 223)
Deceleraon me 2
(Deceleraon me 2)
0.0 ... [5.0] ... 3600.0 s
The deceleraon me set refers to the deceleraon from the maximum
frequency set to standsll. In the case of a lower actual frequency, the
actual deceleraon me is reduced accordingly.
Deceleraon me 2 is acve if
"Motor potenometer" funcon is acve, or
frequency setpoint (absolute value) > auto-change-over threshold
0x291B (PAR 224), or
the trigger assigned in 0x2631:039 (PAR 400/039) of the "Acvate
ramp 2" funcon is TRUE.
Flexible I/O conguraon
Acvang ramp 2 manually
204
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.actechdrives.com - Email: info@actechdrives.com

Table of Contents

Other manuals for Lenze i510

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i510 and is the answer not in the manual?

Lenze i510 Specifications

General IconGeneral
Product CategoryDC Drives
Seriesi510
Protection ClassIP20
CommunicationCANopen, Modbus RTU
Protection FeaturesOvervoltage, Undervoltage
Operating Temperature-10 to +50 °C
Storage Temperature-25 to +70 °C
Humidity5% to 95% (non-condensing)
Control ModeV/f control

Related product manuals