11.7 Acvang ramp 2 manually
The "Acvate ramp 2" funcon serves to manually acvate acceleraon me 2 and deceler
a-
on me 2.
Parameter Name / value range / [default seng] Info
0x2631:039
(PAR 400/039)
Funcon assignment: Acvate ramp 2
(
Funcon list: Acv. ramp 2)
•
For possible sengs see descripon for
0x2631:001 (PAR 400/001). ^ 188
Assignment of a trigger for the "Acvate ramp 2" funcon.
Trigger = TRUE: acvate acceleraon me 2 and deceleraon me 2
manually.
Trigger = FALSE: no acon / deacvate funcon again.
Notes:
•
Acceleraon me 2 and deceleraon me 2 are also acve if the
"Motor potenometer" funcon is acve or the frequency setpoint
(absolute value) > auto-changeover threshold 0x291B (PAR 224).
•
Acceleraon me 2 can be set in 0x2919 (PAR 222).
•
Deceleraon me 2 can be set in 0x291A (PAR 223).
00 Not connected No trigger assigned (trigger is constantly FALSE).
0x2917
(PAR 220)
Acceleraon me 1
(Acceleraon me 1)
0.0 ... [5.0] ... 3600.0 s
The acceleraon me set refers to the acceleraon from standsll to the
maximum frequency set. In the case of a lower setpoint selecon, the
actual acceleraon me is reduced accordingly.
0x2918
(PAR 221)
Deceleraon me 1
(Deceleraon me 1)
0.0 ... [5.0] ... 3600.0 s
The deceleraon me set refers to the deceleraon from the maximum
frequency set to standsll. In the case of a lower actual frequency, the
actual deceleraon me is reduced accordingly.
0x2919
(PAR 222)
Acceleraon me 2
(Acceleraon me 2)
0.0 ... [5.0] ... 3600.0 s
The acceleraon me set refers to the acceleraon from standsll to the
maximum frequency set. In the case of a lower setpoint selecon, the
actual acceleraon me is reduced accordingly.
Acceleraon me 2 is acve if
•
"Motor potenometer" funcon is acve, or
•
frequency setpoint (absolute value) > auto-change-over threshold
0x291B (PAR 224), or
•
the trigger assigned in 0x2631:039 (PAR 400/039) of the "Acvate
ramp 2" funcon is TRUE.
0x291A
(PAR 223)
Deceleraon me 2
(Deceleraon me 2)
0.0 ... [5.0] ... 3600.0 s
The deceleraon me set refers to the deceleraon from the maximum
frequency set to standsll. In the case of a lower actual frequency, the
actual deceleraon me is reduced accordingly.
Deceleraon me 2 is acve if
•
"Motor potenometer" funcon is acve, or
•
frequency setpoint (absolute value) > auto-change-over threshold
0x291B (PAR 224), or
•
the trigger assigned in 0x2631:039 (PAR 400/039) of the "Acvate
ramp 2" funcon is TRUE.
Flexible I/O conguraon
Acvang ramp 2 manually