4.4.3 Basic motor sengs
Check the following default sengs for the motor and motor control and adapt them, if
required.
Drive behaviour b
y default
By default, the V/f characterisc control with a linear characterisc is preset as motor control
for asynchronous motors. The V/f characterisc control is a motor control for convenonal
frequency inverter applicaons. It is based on a simple and robust control mode for the opera-
on of asynchronous motors with a linear or square-law load torque characterisc (e.g. fan).
Because of the minimal parameterisaon eort, such applicaons can be commissioned easily
and quickly.
The default sengs of the parameters ensure that the inverter is ready for operaon imme-
diately and the motor works adequately without further parameterisaon if an inverter and
a 50 Hz asynchronous machine with matching performances are assigned to each other.
Parameter Name / value range / [default seng] Info
0x2B01:001
(PAR 303/001)
V/f characterisc data
: Base voltage
(V/f char. data: Base voltage)
0 ... [230]* ... 5000 V
•
Default seng depending on the size.
Voltage in the reference point of the V/f characterisc.
•
The V/f base voltage is usually se
t to the rated motor voltage
0x2C01:007 (PAR 320/007).
0x2B01:002
(PAR 303/002)
V/f characterisc data
: Base frequency
(V/f char. data: Base frequency)
0 ... [50]* ... 599 Hz
•
Default seng depending on the size.
Frequency in the reference point of the V/f characterisc.
•
The V/f base frequency is usually set to the r
ated motor frequency
0x2C01:005 (PAR 320/005).
0x2C00
(PAR 300)
Motor contr
ol type
(Motor ctrl mode)
•
Seng can only be changed if controller inhibit is
acve.
Selecon of the motor control type.
4 Sensorless vector control (SLVC) This control type is used for sensorless vector control of an asynchro-
nous motor.
4Sensorless vect
or control (SLVC) ^ 82
6 V/f characterisc control (VFC open loop) This control mode is used for the speed control of an asynchronous
motor via a V/f characterisc and is the simplest con
trol mode.
4V/f characterisc control ^ 81
0x2C01:010 Motor parameters: Name
0x6075
(PAR 323)
Motor rat
ed current
(Motor current)
0.001 ... [1.700]* ... 500.000 A
•
Default seng depending on the size.
•
Seng can only be changed if controller inhibit is
acve.
The rated motor current to be set here serves as a reference value for
dierent parameters with a seng/display in percent.
Relevant parameters:
•
DC braking: Current 0x2B84:001 (PAR 704/001)
•
Flying restart circuit: Current 0x2BA1:001 (PAR 718/001)
•
Motor overload monitoring (i²*t): Maximum ulisaon [60 s] 0x2D4B:
001 (PAR 308/001)
•
Max current 0x6073 (PAR 324)
•
Current actual value 0x6078 (PAR 103)
All possible sengs with regard to the motor and motor control are described in the "Motor
control" chap
ter. ^ 77
Commissioning
P
ar
ame
t
er seng
Basic mot
or sengs
20