4.4.3 Basic motor sengs
Check the following default sengs for the motor and motor control and adapt them, if
required.
Drive behaviour b
y default
By default, the V/f characterisc control with a linear characterisc is preset as motor control
for asynchronous motors. The V/f characterisc control is a motor control for convenonal
frequency inverter applicaons. It is based on a simple and robust control mode for the opera-
on of asynchronous motors with a linear or square-law load torque characterisc (e.g. fan).
Because of the minimal parameterisaon eort, such applicaons can be commissioned easily
and quickly.
The default sengs of the parameters ensure that the inverter is ready for operaon imme-
diately and the motor works adequately without further parameterisaon if an inverter and
a 50 Hz asynchronous machine with matching performances are assigned to each other.
Parameter Name / value range / [default seng] Info
0x2B01:001
(PAR 303/001)
V/f characterisc data
: Base voltage
(V/f char. data: Base voltage)
0 ... [230]* ... 5000 V
Default seng depending on the size.
Voltage in the reference point of the V/f characterisc.
The V/f base voltage is usually se
t to the rated motor voltage
0x2C01:007 (PAR 320/007).
0x2B01:002
(PAR 303/002)
V/f characterisc data
: Base frequency
(V/f char. data: Base frequency)
0 ... [50]* ... 599 Hz
Default seng depending on the size.
Frequency in the reference point of the V/f characterisc.
The V/f base frequency is usually set to the r
ated motor frequency
0x2C01:005 (PAR 320/005).
0x2C00
(PAR 300)
Motor contr
ol type
(Motor ctrl mode)
Seng can only be changed if controller inhibit is
acve.
Selecon of the motor control type.
4 Sensorless vector control (SLVC) This control type is used for sensorless vector control of an asynchro-
nous motor.
4Sensorless vect
or control (SLVC) ^ 82
6 V/f characterisc control (VFC open loop) This control mode is used for the speed control of an asynchronous
motor via a V/f characterisc and is the simplest con
trol mode.
4V/f characterisc control ^ 81
0x2C01:010 Motor parameters: Name
0x6075
(PAR 323)
Motor rat
ed current
(Motor current)
0.001 ... [1.700]* ... 500.000 A
Default seng depending on the size.
Seng can only be changed if controller inhibit is
acve.
The rated motor current to be set here serves as a reference value for
dierent parameters with a seng/display in percent.
Relevant parameters:
DC braking: Current 0x2B84:001 (PAR 704/001)
Flying restart circuit: Current 0x2BA1:001 (PAR 718/001)
Motor overload monitoring (i²*t): Maximum ulisaon [60 s] 0x2D4B:
001 (PAR 308/001)
Max current 0x6073 (PAR 324)
Current actual value 0x6078 (PAR 103)
All possible sengs with regard to the motor and motor control are described in the "Motor
control" chap
ter. ^ 77
Commissioning
P
ar
ame
t
er seng
Basic mot
or sengs
20
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.actechdrives.com - Email: info@actechdrives.com

Table of Contents

Other manuals for Lenze i510

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i510 and is the answer not in the manual?

Lenze i510 Specifications

General IconGeneral
Product CategoryDC Drives
Seriesi510
Protection ClassIP20
CommunicationCANopen, Modbus RTU
Protection FeaturesOvervoltage, Undervoltage
Operating Temperature-10 to +50 °C
Storage Temperature-25 to +70 °C
Humidity5% to 95% (non-condensing)
Control ModeV/f control

Related product manuals