11.9 Funcons for parameter change-over
The inverter supports several parameter sets. The parameter set can be selected by means of
the "Paramet
er set selecon bit 0" and "Parameter set selecon bit 1" funcons.
Details
A value set is selected in a binary-coded fashion via the triggers assigned to the two Parameter
set selecon bit 0" and " Parameter set selecon bit 1" funcons in compliance with the fol-
lowing truth table:
Parameter set selecon bit 1 Parameter set selecon bit 0 Selecon
FALSE FALSE Value set 1
FALSE TRUE Value set 2
TRUE FALSE Value set 3
TRUE TRUE Value set 4
Change-over is eected depending on the acvaon method selected in 0x4046 (PAR 755)
when a s
tate change of the selecon inputs takes place or via the trigger assigned to the
"Load parameter set" funcon.
Parameter Name / value range / [default seng] Info
0x2631:040
(PAR 400/040)
Funcon assignment: Load paramet
er set
(Funcon list: Load param.set)
•
Seng can only be changed if controller inhibit is
acve.
•
For possible sengs see descripon for
0x2631:001 (PAR 400/001). ^ 188
Assignment of a trigger for the "Load parameter set" funcon.
Trigger = FALSE-TRUE edge: parameter change-over to the value set
selected via "Parameter set selecon bit 0" and "Parameter set selecon
bit 1".
Trigger = FALSE: no acon.
Notes:
•
The acvaon method for the "Parameter change-over" funcon can
be selected in 0x4046 (PAR 755).
00 Not connected No trigger assigned (trigger is constantly FALSE).
0x2631:041
(PAR 400/041)
Funcon assignment: Parameter set selecon bit 0
(Funcon list: Par.set selecon b0)
•
Seng can only be changed if controller inhibit is
acve.
•
For possible sengs see descripon for
0x2631:001 (PAR 400/001). ^ 188
Assignment of a trigger for the "Parameter set selecon bit 0" funcon.
Selecon bit with the valency 2
0
for "Parameter change-over" funcon.
Trigger = FALSE: selecon bit = "0".
Trigger = TRUE: selecon bit = "1".
00 Not connected No trigger assigned (trigger is constantly FALSE).
0x2631:042
(PAR 400/042)
Funcon assignment: Parameter set selecon bit 1
(Funcon list: Par.set selecon b1)
•
Seng can only be changed if controller inhibit is
acve.
•
For possible sengs see descripon for
0x2631:001 (PAR 400/001). ^ 188
Assignment of a trigger for the "Parameter set selecon bit 1" funcon.
Selecon bit with the valency 2
1
for "Parameter change-over" funcon.
Trigger = FALSE: selecon bit = "0".
Trigger = TRUE: selecon bit = "1".
00 Not connected No trigger assigned (trigger is constantly FALSE).
0x4046
(PAR 755)
Acvaon of parameter set
(Param. set mode)
Selecon of the acvaon method for the parameter change-over.
0 Via command (only if the controller is
inhibited)
The parameter se
t selected via the "Parameter set selecon bit 0" and
"Parameter set selecon bit 1" funcons is acvated if the trigger
assigned in 0x2631:040 (PAR 400/040) of the "Load parameter set" func-
on supplies a FALSE-TRUE edge AND the inverter is inhibited.
1 Via command (immediately) The parameter set selected via the "Parameter set selecon bit 0" and
"Parameter set selecon bit 1" funcons is acvated if the trigger
assigned in 0x2631:040 (PAR 400/040) of the "Load parameter set" func-
on supplies a FALSE-TRUE edge.
2 If the selecon is changed (only if the
controller is inhibited)
The parameter set selected via the "Parameter set selecon bit 0" and
"Parameter set selecon bit 1" funcons is acvated if a state change of
these selecon bits takes place AND the inverter is inhibited.
3 If the selecon is changed (immediately) The parameter set selected via the "Parameter set selecon bit 0" and
"Parameter set selecon bit 1" funcons is acvated if a state change of
these selecon bits takes place.
Flexible I/O conguraon
Funcons for parameter change-over
206