11.13 Conguraon of analog inputs
11.13.1 Analog input 1
Sengs for analog input 1.
Details
The in
ternal output signal of the analog input is either a frequency setpoin
t or a process
controller setpoint that is calculated from the percentage input value.
The seng range can be individually dened for speed mode and process c
ontroller mode.
Oponally, a dead band can be congured. Setpoints in this range that are centred around
0 Hz are ignored which is used to eliminate smallest signal levels for the setpoint frequency
0 Hz.
Denion of the seng range and dead band for speed mode
0
100-100
[Hz]
[%]
Parameter Name Notes
0x2636:003 (PAR 430/003) Max value [Hz]
0x2636:002 (PAR 430/002) Min value [Hz] For all modes except -10 V ... +10 V
Only for mode -10 V ... +10 V
0x2636:007 (PAR 430/007) Dead band A seng > 0 produces a dead band to the zero
crossing of the [Hz] axis. The value set denes
half the width of the dead band in [%].
Parameter Name / value range / [default seng] Info
0x2636:001
(PAR 430/001)
Analog input 1: Input range
(Analog input 1
: AI1 cong.)
Denion of the input range.
0 0 … 10 VDC
1 0 … 5 VDC
2 2 … 10 VDC
3 -10 … +10 VDC
4 4 … 20 mA
5 0 … 20 mA
0x2636:002
(PAR 430/002)
Analog input 1: Min value [Hz]
(Analog input 1: AI1 freq @ min)
-1000.0 ... [0.0] ... 1000.0 Hz
Denion of the seng range for speed mode.
A negave seng only shis the oset, but does not change the
rotang direcon.
The rotang direcon is reversed if Min value [Hz] > Max value [Hz] is
set.
0x2636:003
(PAR 430/003)
Analog input 1: Max value [Hz]
(Analog input 1: AI1 freq @ max)
-1000.0 ... [50.0] ... 1000.0 Hz
0x2636:004
(PAR 430/004)
Analog input 1: Min value [Punit/%]
(Analog input 1: AI1 PID/Mom@min)
-300.00 ... [0.00] ... 300.00 PUnit/%
Denion of the seng range for process controller mode and torque
mode.
0x2636:005
(PAR 430/005)
Analog input 1: Max value [Punit/%]
(Analog input 1: AI1 PID/Mom@max)
-300.00 ... [100.00] ... 300.00 PUnit/%
Flexible I/O conguraon
Conguraon of analog inputs
Analog input 1