Parameter Name / value range / [default seng] Info
0x2636:006
(PAR 430/006)
Analog input 1: Filter me
(Analog input 1: AI1 lter
me)
0 ... [10] ... 10000 ms
PT1 me constant for low-pass lter.
•
By the use of a low-pass lter, the impacts of noise to an analog signal
c
an be minimised.
•
For an opmum lter eect,
rst the noise frequency has to be deter-
mined. The me constant then has to be set so that it equals the
reciprocal value of the double frequency.
0x2636:007
(PAR 430/007)
Analog input 1: Dead band
(Analog input 1: AI1 dead band)
0.0 ... [0.0] ... 100.0 %
Oponal seng of a dead band that is placed symmetrically around the
frequency zero point.
•
The value set denes half the width of the dead band in [%].
•
If the analog input value is within the dead band, the output value for
the motor control is set to "0".
0x2636:008
(PAR 430/008)
Analog input 1: Monitoring threshold
(Analog input 1
: AI1 monit.level)
-100.0 ... [0.0] ... 100.0 %
Trigger threshold for monitoring the analog input.
•
100 % ≡ 10 V (with conguraon as voltage input)
•
100 % ≡ 20 mA (with conguraon as current loop)
0x2636:009
(PAR 430/009)
Analog input 1: Monitoring condion
(Analog input 1: AI1 monit.acon)
T
rigger condion for monitoring the analog input.
•
If the trigger condion is met for at least 500 ms, the response set in
subindex 10 is eected.
0 Input value < trigger threshold Input value < trigger threshold
1 Input value > trigger threshold Input value > trigger threshold
0x2636:010
(PAR 430/010)
Analog input 1: Monitoring response
(Analog input 1: AI1 error resp.)
•
For possible sengs see descripon for
0x2D45:001 (PAR 310/001). ^ 94
Selecon of the response to the triggering of the analog input monitor-
ing.
•
If a response is set, the "Error of analog input 1" trigger is also set to
TRUE when the monitoring funcon is acvated. The user can ulise
this trigger to acvate specic funcons.
3 Error
Flexible I/O conguraon
Conguraon of analog inputs
Analog input 1
212