5.3.4.2 Modbus diagnoscs
The following parameters serve to diagnose the Modbus interface and communicaon via
Modbus.
Precondions
Control unit (CU) of the inverter is provided with Modbus.
Parameter Name / value range / [default seng] Info
0x2322:001
(PAR 511/001)
Acve Modbus sengs: Node ID
(Acve se.: Node ID)
Read only
Displa
y of the acve node address.
0x2322:002
(PAR 511/002)
Acve Modbus sengs: Baud rate
(Acve se.: Baud rate)
Read only
Display of the acve baud rate.
0x2322:003
(PAR 511/003)
Acve Modbus sengs: Data forma
t
(Acve se.: Data format)
Read only
Display of the acve data format.
0x232A:001
(PAR 580/001)
Modbus stascs: Messages received
(Modbus c
ounter: Messages received)
Read only
Display of the total number of messages received.
This counter counts both valid and invalid messages.
Aer the maximum value has been reached, the counter starts again
"0".
0x232A:002
(PAR 580/002)
Modbus stascs: Valid messages received
(Modbus counter: Val. mess. rec.)
Read only
Display of the number of valid messages received.
Aer the maximum value has been reached, the counter starts again
"0".
0x232A:003
(PAR 580/003)
Modbus stascs: Messages with excepons
(Modbus counter: Mess. w. exc.)
Read only
Display of the number of messages with excepons that have been
received.
Aer the maximum value has been reached, the counter starts again
"0".
0x232A:004
(PAR 580/004)
Modbus stascs: Messages with errors
(Modbus counter: Mess. with errors)
Read only
Display of the number of messages received with a faulty data integrity
(parity, CRC).
Aer the maximum value has been reached, the counter starts again
"0".
0x232A:005
(PAR 580/005)
Modbus stascs: Messages sent
(Modbus coun
ter: Messages sent)
Read only
Display of the total number of messages sent.
Aer the maximum value has been reached, the counter starts again
"0".
Related topics
4Modbus ^ 127
5.3.5 Diagnoscs of the inputs and outputs
5.3.5.1 Digital inputs and outputs
The following par
ameters serve to diagnose the digital inputs and outputs of the inverter.
Parameter Name / value range / [default seng] Info
0x60FD
(PAR 118)
Digital inputs
(Dig.inp. status
)
Read only
Bit coded display of the current state of the digital inputs
Bit 0 Reserved -
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Diagnoscs and fault eliminaon
Diagnoscs
Diagnoscs of the inputs and outputs
57