6.3 Selecon of setpoint source
"Setpoint sources" are the signal sources from which the inverter receives its setpoints for the
dierent operang modes.
Possible setpoint sources are:
•
Analog inputs
•
Keypad
•
Process input dat
a (network)
•
Parameterisable setpoints (preset values)
•
"Motor potenometer" funcon
Details
•
For applicaons only requiring one setpoint it is sucient t
o dene the standard setpoint
source in the follo
wing parameters.
•
For applicaons requiring a change-over of the setpoint source during operaon, the func-
on assignment of the funcons for the setpoint selecon has to be congured correspond-
ingly. 4Flexible I/O conguraon ^ 186
Parameter Name / value range / [default seng] Info
0x2860:001
(PAR 201/001)
Standard setpoin
t sources: Frequency setpoint source
(Standard setpoint: Frequency setp.)
Selecon of the standard setpoint source for speed mode.
•
The standard setpoint source is always acve in speed mode if no set-
point change-over to another setpoint source via corresponding trig-
gers/funcons is acve.
4Setpoint change-over ^ 193
1 K
eypad The setpoint is specied locally by the keypad.
•
Default seng: 0x2601:001 (PAR 202/001)
•
Use the
and navigaon keys to change the keypad setpoint
(also during running operaon).
2 Analog input 1 The setpoin
t is specied analogously via X3/AI1.
4Analog input 1 ^ 211
3 Analog input 2 The setpoint is specied analogously via X3/AI2.
4Analog input 2 ^ 213
5 Network The setpoint is specied via network.
4
Conguring the network ^
96
11 Preset frequency val. 1 For the setpoint selecon, preset values can be parameterised and selec-
ted.
4Setpoint source of preset setpoints ^ 195
12 Preset frequency val. 2
13 Preset frequency val. 3
14 Preset frequency val. 4
15 Preset frequency val. 5
16 Preset frequency val. 6
17 Preset frequency val. 7
18 Preset frequency val. 8
19 Preset frequency val. 9
20 Preset frequency val. 10
21 Preset frequency val. 11
22 Preset frequency val. 12
23 Preset frequency val. 13
24 Preset frequency val. 14
25 Preset frequency val. 15
50 Motor potenometer The setpoint is generated by the "Motor potenometer" funcon.
4Motor potenometer setpoint source
^ 198
0x2860:002
(PAR 201/002)
Standard setpoint sources: Process controller setpoint
source
(Standard setpoint: PID setpoint)
Selecon of the standard setpoint source for process controller mode.
•
The standard setpoint source is always acve in process controller
mode if no setpoint change-over to another setpoint source via corre-
sponding triggers/funcons is acve.
1 Keypad The setpoint is specied locally by the keypad.
•
Default seng: 0x2601:002 (PAR 202/002)
•
Use the
and navigaon keys to change the keypad setpoint
(also during running operaon).
Basic seng
Selecon of setpoint source