6.3 Selecon of setpoint source
"Setpoint sources" are the signal sources from which the inverter receives its setpoints for the
dierent operang modes.
Possible setpoint sources are:
Analog inputs
Keypad
Process input dat
a (network)
Parameterisable setpoints (preset values)
"Motor potenometer" funcon
Details
For applicaons only requiring one setpoint it is sucient t
o dene the standard setpoint
source in the follo
wing parameters.
For applicaons requiring a change-over of the setpoint source during operaon, the func-
on assignment of the funcons for the setpoint selecon has to be congured correspond-
ingly. 4Flexible I/O conguraon ^ 186
Parameter Name / value range / [default seng] Info
0x2860:001
(PAR 201/001)
Standard setpoin
t sources: Frequency setpoint source
(Standard setpoint: Frequency setp.)
Selecon of the standard setpoint source for speed mode.
The standard setpoint source is always acve in speed mode if no set-
point change-over to another setpoint source via corresponding trig-
gers/funcons is acve.
4Setpoint change-over ^ 193
1 K
eypad The setpoint is specied locally by the keypad.
Default seng: 0x2601:001 (PAR 202/001)
Use the
and navigaon keys to change the keypad setpoint
(also during running operaon).
2 Analog input 1 The setpoin
t is specied analogously via X3/AI1.
4Analog input 1 ^ 211
3 Analog input 2 The setpoint is specied analogously via X3/AI2.
4Analog input 2 ^ 213
5 Network The setpoint is specied via network.
4
Conguring the network ^
96
11 Preset frequency val. 1 For the setpoint selecon, preset values can be parameterised and selec-
ted.
4Setpoint source of preset setpoints ^ 195
12 Preset frequency val. 2
13 Preset frequency val. 3
14 Preset frequency val. 4
15 Preset frequency val. 5
16 Preset frequency val. 6
17 Preset frequency val. 7
18 Preset frequency val. 8
19 Preset frequency val. 9
20 Preset frequency val. 10
21 Preset frequency val. 11
22 Preset frequency val. 12
23 Preset frequency val. 13
24 Preset frequency val. 14
25 Preset frequency val. 15
50 Motor potenometer The setpoint is generated by the "Motor potenometer" funcon.
4Motor potenometer setpoint source
^ 198
0x2860:002
(PAR 201/002)
Standard setpoint sources: Process controller setpoint
source
(Standard setpoint: PID setpoint)
Selecon of the standard setpoint source for process controller mode.
The standard setpoint source is always acve in process controller
mode if no setpoint change-over to another setpoint source via corre-
sponding triggers/funcons is acve.
1 Keypad The setpoint is specied locally by the keypad.
Default seng: 0x2601:002 (PAR 202/002)
Use the
and navigaon keys to change the keypad setpoint
(also during running operaon).
Basic seng
Selecon of setpoint source
70