11.8 Triggering a user-dened fault
The "User-dened fault 1" and "User-dened fault 2" funcons serve to set the inverter from
the process to the error st
atus.
Details
If, for instance, sensors or switches are provided for process monitoring, which are designed
to stop the process (and thus the drive) under certain condions, these sensors/switches can
be connected to free digital inputs of the inverter. The digital inputs used for the sensors/
switches then have to be assigned to the error triggering funcons as triggers.
Parameter Name / value range / [default seng] Info
0x2631:043
(PAR 400/043)
Funcon assignment: User-dened fault 1
(
Funcon list: User-def fault 1)
•
For possible sengs see descripon for
0x2631:001 (PAR 400/001). ^ 188
Assignment of a trigger for the "User-dened fault 1" funcon.
Trigger = TRUE: trigger user-dened fault 1.
Trigger = FALSE: no acon.
Notes:
•
When the fault has been triggered, the inverter changes to the "Trou-
ble" state.
•
Aer reseng the fault, a new enable/start command is required to
restart the drive.
00 Not connected No trigger assigned (trigger is constantly FALSE).
0x2631:044
(PAR 400/044)
Funcon assignment: User-dened fault 2
(Funcon list: User-def fault 2)
•
For possible sengs see descripon for
0x2631:001 (PAR 400/001). ^ 188
Assignment of a trigger for the "User-dened fault 2" funcon.
Trigger = TRUE: trigger user-dened fault 2.
Trigger = FALSE: no acon.
Notes:
•
When the fault has been triggered, the inverter changes to the "Trou-
ble" state.
•
Aer reseng the fault, a new enable/start command is required to
restart the drive.
00 Not connected No trigger assigned (trigger is constantly FALSE).
Flexible I/O conguraon
Triggering a user-dened fault
205