8.2.3 Lenze LECOM prole
For connecon to Lenze inverters with a LECOM control word (C135) and LECOM status word
(C150), the parameters lis
ted in the following can be mapped to network registers.
Details
The LECOM contr
ol word (C135) features the mapping address 0x400B0200.
The LECOM status word (C150) features the mapping address 0x400C0200.
General informaon about the process of data mapping can be found in the chapter of the
same name for the corresponding netw
ork.
Parameter Name / value range / [default seng] Info
0x400B:002
(PAR 592/002)
Predened process input data
: LECOM control word
(C135)
(Legacy NetWordIN: C0135 control word)
0x0000 ... [0x0000] ... 0xFFFF
Mappable control word with bit assignment in compliance with code
C135 of the 8200 Lenze inverter.
Bit 0 Setpoint Selecon bit 0
Bit 1 Setpoint Selecon bit 1
Bit 2 Reversal
Bit 3 Quick stop
Bit 4 Reserved
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9 Controller inhibit
Bit 10 User-dened fault
Bit 11 Reset error (0-1 edge)
Bit 12 Reserved
Bit 13
Bit 14 DC braking
Bit 15 Reserved
0x400C:002
(PAR 593/002)
Predened process output data: LECOM status word
(C150)
(Old netw. o: C0150 status word)
Read only
Mappable status word with bit assignment in compliance with code
C150 of the 8200 Lenze inverter.
Bit 0 Acve parameter set (0 = set 1 or 3; 1 = set 2
or 4)
Bit 1 Power secon inhibited
Bit 2 Current or Torque limit reached
Bit 3 Frequency setpoint reached
Bit 4 Ramp generator (input = output)
Bit 5 Frequency < frequency threshold
Bit 6 Actual frequency = 0
Bit 7 Controller inhibit
Bit 8 Coded status bit 0
Bit 9 Coded status bit 1
Bit 10 Coded status bit 2
Bit 11 Coded status bit 3
Bit 12 Overtemperature warning
Bit 13 DC-bus overvoltage
Bit 14 Reversal
Bit 15 Ready for Operaon
Conguring the network
Predened process data words
Lenze LECOM prole
107
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.actechdrives.com - Email: info@actechdrives.com

Table of Contents

Other manuals for Lenze i510

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i510 and is the answer not in the manual?

Lenze i510 Specifications

General IconGeneral
Product CategoryDC Drives
Seriesi510
Protection ClassIP20
CommunicationCANopen, Modbus RTU
Protection FeaturesOvervoltage, Undervoltage
Operating Temperature-10 to +50 °C
Storage Temperature-25 to +70 °C
Humidity5% to 95% (non-condensing)