6.4 Starng/stopping performance
6.4.1 Starng performance
Parameter Name / value range / [default seng] Info
0x2838:001
(PAR 203/001)
Start/st
op conguraon: Start method
(Start/stop confg: Start method)
•
Seng can only be changed if controller inhibit is
acve.
Starng performance of the inverter.
0 Normal Aer switch-on, the standard ramps are acve.
•
Acceleraon me 1 can be set in 0x2917 (PAR 220).
•
Deceleraon me 1 can be set in 0x2918 (PAR 221).
1 Start with DC braking Aer switch-on, the "DC braking" funcon is acve for the me set in
0x2B84:002 (PAR 704/002).
4DC braking ^
153
2 Flying Start Aer switch-on, the "Restart on the y"
funcon is acve.
This funcon mak
es it possible t
o r
es
tart a coasng motor on the y dur-
ing operaon without speed feedback. Synchronicity between the inver-
ter and the motor is coordinated so that the transion to the rotang
drive is eected without jerk at the me of connecon.
4Flying restart funcon ^ 182
0x2838:002
(PAR 203/002)
St
art/stop conguraon: Start at switch-on
(Start/stop confg: Start at switch-on)
Behaviour aer mains connecon.
0 O If the controller is enabled at mains power-up, the inverter remains in
the "Ready to switch on" state.
For a change-over to the "Switched on" state, controller enable must be
deacvated rst. Only with the following controller enable, a change-
over to the "Operaon enabled" state is eected, and the motor follows
the setpoint specied.
1 On If the controller is enabled at mains power-up, aer mains power-up the
motor directly follows the setpoint specied.
With this seng, the inverter directly changes from the "Ready to switch
on" state to the "Switched on" state and then to the "Operaon
enabled" state.
6.4.2 Stopping performance
Parameter Name / value range / [default seng] Info
0x2838:003
(P
AR 203/003)
St
art/
s
t
op conguraon: Stop method
(Start/stop confg: Stop method)
Behaviour aer the "Stop" command.
0 Coasng The motor coasts down to standsll.
1 Standard Ramp The motor is brought to a standsll with deceleraon me 1 (or deceler-
aon me 2, if acvated).
•
Deceleraon me 1 can be set in 0x2918 (PAR 221).
•
Deceleraon me 2 can be set in 0x291A (PAR 223).
4Frequency limits and ramp mes ^ 73
2 Quick stop ramp The motor is brought to a standsll with the deceleraon me set for
the "Quick s
t
op" funcon.
•
Deceleraon
me f
or quick stop can be set in 0x291C (P
AR 225).
Basic seng
Starng/stopping performance
Starng performance