Parameter Name / value range / [default seng] Info
Bit 1 Digital output 1 0 ≡ LOW level, 1 ≡ HIGH level.
Bit 2 Digital output 2
Bit 3 Reserved -
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10 Charge Relay
Bit 11 Reserved -
Bit 12
Bit 13
Bit 14
Bit 15
0x603F
(PAR 150)
Error code
(Acve error
)
Read only
Error message
5.3.4 Network diagnoscs
The following parameters show some general informaon with regard to the network opon
available and the network.
Further eldbus-specic diagnosc parameters are described in the following subchapters.
Parameter Name / value range / [default seng] Info
0x282B:005
(PAR 125/005)
Inverter diagnoscs:
Most recently used control
register
(Inverter diag.: Netw. contr.reg.)
Read only
Display of the network register for the control that was accessed last
(e. g. 0x6040 or 0x400B:1).
Format: 0xiiiiss00 (iiii = hexadecimal index, ss = hexadecimal subindex)
The lowest byte is always 0x00.
0x282B:006
(PAR 125/006)
Inverter diagnoscs: Most recently used setpoint
register
(Inverter diag.: Netw. setp.reg.)
Read only
Display of the network register for setpoint selecon that was accessed
last (e. g. 0x6042 or 0x400B:3).
Format: 0xiiiiss00 (iiii = hexadecimal index, ss = hexadecimal subindex)
The lowest byte is always 0x00.
0x400B:006
(PAR 592/006)
Predened process input data: Network speed
setpoint
(Legacy NetWordIN: Netw. speed setp.)
-599.0 ... [0.0] ... 599.0 Hz
Display of the setpoint received via network for speed mode.
0x400B:007
(PAR 592/007)
Predened process input data: Network process
controller setpoint
(Legacy NetWordIN: Netw. PID setp.)
-300.00 ... [0.00] ... 300.00 PUnit
Display of the setpoint received via network for process controller mode.
0x400B:008
(PAR 592/008)
Predened process input data: Network torque
setpoint
(Legacy NetWordIN: Netw. torque setp.)
-32768 ... [0] ... 32767 Nm
Display of the setpoint received via network for torque mode.
0x231F:001
(PAR 500/001)
Module ID: Acve module ID
(Module ID: Acve module ID)
Read only
Default seng depending on the size.
Display of the network opons currently congured in the inverter.
When the "Load Lenze sengs" device command 0x2022:001
(PAR 700/001)or "Accept new inverter hardware" 0x2022:027
(PAR 700/027) is executed, the module ID is stored in the memory
module.
With the help of this module ID, the keypad only shows the communi-
caon parameters relevant to the respecve network.
0 No network
67 CANopen
80 PROFIBUS
87 Modbus
Diagnoscs and fault eliminaon
Diagnoscs
Network diagnoscs
53