8.1 General network sengs
Checking the network opon
A
t switch-on, the inverter checks whether the parameter sengs saved in the memory mod-
ule match the network opon available in the control unit. If this is not the case, the inverter
assumes the error status. The error status can only be exited by accepng the currently availa-
ble network opon as new hardware. For this purpose, 0x2022:027 (PAR 700/027) must be set
to "1". When this device command is executed, all parameters for the new network opon are
inialised.
Diagnosc parameters:
The network opon currently congured in the inverter is displayed in 0x231F:001
(PAR 500/001).
The network opon currently available in the inverter is displayed in 0x231F:002
(PAR 500/002).
Enabling the network as control source
In order to be able to control the inverter via network, a trigger must rst be assigned in
0x2631:037 (PAR 400/037) of the "Network enable" funcon. This trigger can for instance be
the constant value "TRUE" or a digital input. If the trigger assigned is TRUE, the inverter
changes to the network control mode. The inverter now responds to the start and stop com-
mands received via network.
In network control mode the following funcons are sll acve:
0x2631:001 (PAR 400/001): Controller enable
0x2631:002 (PAR 400/002): St
art enable
0x2631:003 (PAR 400/003): Quick stop
0x2631:004 (PAR 400/004): Reset error
0x2631:005 (PAR 400/005): DC braking
0x2631:037 (PAR 400/037): Network enable
All other funcons that can be congured via 0x2631 (PAR 400) are deacvated in network
control mode.
Netw
ork control word and status word
For establishing a simple network connecon, the inverter provides predened control and
status words for device prole CiA402, AC drive prole as well as in LECOM format. By means
of data mapping to a network register, each of these words can be transferred as process date
via network.
For the assignment of the predened control and status words see the following chapters:
Device prole CiA402. ^ 105
AC Drive Prole. ^ 106
Lenze LECOM prole. ^ 107
If an individual control word format is to be implemented, the NETwordIN1 data word is provi-
ded for this purpose.
The NETwordIN1 data word features the mapping address 0x40080100 (index 0x4008:001).
The funcons which are to be triggered via bits 1 ... 16 of the NETwordIN1 data word are
dened in 0x400E:001 (PAR 505/001).
If an individual status word format is to be implemented, the NETwordOUT1 data word is pro-
vided for this purpose.
The NETwordOUT1 data word features the mapping address 0x400A0100 (index 0x400A:
001).
The trigger for bits 1 ... 16 of the NETwordOUT1 data word is dened in 0x2634:010
(PAR 420/010) ... 0x2634:025 (PAR 420/025).
General informaon about the process of data mapping can be found in the chapter of the
same name for the corresponding network.
Conguring the network
General network sengs
97