Network setpoint
In or
der t
o g
ener
ally se
t the network as standard setpoint source, go to 0x2860:001
(PAR 201/001) and select "Network [5]".
If a bit of the mappable NETWordIN1 data word is to be used for acvaon, use 0x400E:001
(PAR 505/001) to assign the funcon "Setpoint = Ne
twork [17]" to the corresponding bit of
NETWordIN1.
There is no specic funcon with a selectable trigger for a setpoint change-over to the net-
work.
Parameter Name / value range / [default seng] Info
0x231F:001
(PAR 500/001)
Module ID: Acve module ID
(Module ID:
Acve module ID)
Read only
Default seng depending on the size.
Display of the network opons currently congured in the inverter.
When the "Load Lenze sengs" device command 0x2022:001
(PAR 700/001)or "Accept new inverter hardware" 0x2022:027
(PAR 700/027) is executed, the module ID is stored in the memory
module.
With the help of this module ID, the keypad only shows the communi-
caon parameters relevant to the respecve network.
0 No network
67 CANopen
80 PROFIBUS
87 Modbus
0x231F:002
(PAR 500/002)
Module ID: Module ID connected
(Module ID: Module ID conn.)
Read only
Display of the network opons currently connected in the inverter.
0 No network
67 CANopen
80 PROFIBUS
87 Modbus
0x400E:001
(PAR 505/001)
NETWordIN1 funcon assignment: Bit 0
(NETWordIN1 cong.: NETWordIN1.00)
Seng can only be changed if controller inhibit is
acve.
Denion of the funcon that is to be triggered via bit 0 of the mappa-
ble NETWordIN1 data word.
0 Not acve Trigger bit without any funcon.
1 Controller inhibit Trigger bit = 0-1 edge: The inverter is inhibited. Starng the drive is not
possible.
Trigger bit = 0: The inverter is enabled (unless there is another cause for
controller inhibit).
Notes:
In all device states, a 0-1 edge causes an immediate change to the
inhibited state with one excepon: If the inverter is in the error status
and the error condion sll exists, the inverter remains in the error
status.
Changing to the inhibited state causes an immediate stop of the drive,
regardless of the stop method set in 0x2838:003 (PAR 203/003). The
drive coasts down as a funcon of the mass inera of the machine.
Aer deacvang the controller inhibit, a new start command is
required to restart the drive.
The causes that are acve for controller inhibit are shown in 0x282A:
001 (PAR 126/001).
2 Stop Trigger bit = 1: Drive is stopped.
Trigger bit = 0: No acon / Deacvate stop again.
Notes:
The stop method can be selected in 0x2838:003 (PAR 203/003).
3 Quick stop Trigger bit = 1: "Quick stop" funcon acvated.
Trigger bit = 0: no acon / deacvate funcon again.
Notes:
The "Quick stop" funcon brings the motor to a standsll within the
deceleraon me set in 0x291C (PAR 225).
The "Quick stop" funcon has a higher priority than the "Start enable"
funcon.
Conguring the network
General network sengs
98