8.2.4 Further process data
The parameters listed in the following can also be mapped to network registers, in order to
transmit control and s
tatus informaon as well as setpoints and actual values as process data.
Details
•
The following paramet
ers are always available irrespecve of the network opon.
•
The use of these parameters for the transmission of process data is oponal. It is also possi-
ble to only use part of the parameter
s. For the transmission of the frequency setpoint and
actual value, for instance several parameters with a dierent resoluon can be selected.
•
Via the parameters, at the same me the general network acvity can be diagnosed.
NetWordIN1 ... NetWordIN4
These four mappable data words are provided to individually control the inverter:
•
NetWordIN1: for the implementaon of an individual control word format. 4General net-
work sengs ^ 97
•
NetWordIN2: for control of the digital outputs via network. 4Conguraon of digital out-
puts ^ 215
•
NetWordIN3 and NetWordIN4: for control of the analog outputs via network. 4Congura-
on of analog outputs^ 221
NetWor
dOUT1 and NetWordOUT2
These two mappable data words are provided to output status messages to the network mas-
ter:
•
NetWordOUT1: for the implementaon of an individual status word format. 4NETWord-
OUT1 status word ^ 218
•
NetWordOUT2: for the output of messages of the "Sequencer" funcon (in preparaon).
Parameter Name / value range / [default seng] Info
0x4008:001
(PAR 590/001)
Process input words
: NETWordIN1
(NETWordIN stat: NETWordIN1)
0x0000 ... [0x0000] ... 0xFFFF
Mappable data word for exible control of the inverter via network.
Assignment of the funcons:
•
0x400E:001 (PAR 505/001): assignment of funcons to bit 0 ... 15.
Bit 0 Mapping bit 0
Bit 1 Mapping bit 1
Bit 2 Mapping bit 2
Bit 3 Mapping bit 3
Bit 4 Mapping bit 4
Bit 5 Mapping bit 5
Bit 6 Mapping bit 6
Bit 7 Mapping bit 7
Bit 8 Mapping bit 8
Bit 9 Mapping bit 9
Bit 10 Mapping bit 10
Bit 11 Mapping bit 11
Bit 12 Mapping bit 12
Bit 13 Mapping bit 13
Bit 14 Mapping bit 14
Bit 15 Mapping bit 15
0x4008:002
(PAR 590/002)
Process input words
: NETWordIN2
(NETWordIN stat: NETWordIN2)
0x0000 ... [0x0000] ... 0xFFFF
Mappable data word for oponal control of the digital outputs via net-
work.
Assignment of the digital outputs:
•
0x2634:001 (PAR 420/001) = 34 ... 49: assignment of the relay output
to bit 0 ... 15.
•
0x2634:002 (PAR 420/002) = 34 ... 49: assignment of digital output 1
to bit 0 ... 15.
•
= 34 ... 49: assignment of digital output 2 to bit 0 ... 15.
Bit 0 Mapping bit 0
Bit 1 Mapping bit 1
Bit 2 Mapping bit 2
Bit 3 Mapping bit 3
Bit 4 Mapping bit 4
Bit 5 Mapping bit 5
Bit 6 Mapping bit 6
Bit 7 Mapping bit 7
Conguring the network
Predened process data words
Further process data