8.2.2 AC Drive Prole
For control via AC drive prole, the parameters listed in the following can be mapped to net-
work register
s.
Details
•
The AC Drive contr
ol word features the mapping address 0x400B0100.
•
The AC Drive status word features the mapping address 0x400C0100.
•
General informaon about the process of data mapping c
an be found in the chapter of the
same name for the corresponding network.
Parameter Name / value range / [default seng] Info
0x400B:001
(PAR 592/001)
Predened process input data
: AC Drive control word
(Legacy NetWordIN: AC control word)
0x0000 ... [0x0000] ... 0xFFFF
Mappable control word with bit assignment in compliance with Ether-
Net/IP™ AC drive prole.
Bit 0 Run forward
Bit 1 Run reverse
Bit 2 Reset error (0-1 edge)
Bit 3 Reserved
Bit 4
Bit 5 Control from Network
Bit 6 Reference from Network
Bit 7 Reserved
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12 Controller inhibit
Bit 13 Quick stop
Bit 14 Process controller o
Bit 15 DC braking
0x400C:001
(PAR 593/001)
Predened process output data: AC Drive status word
(Old netw. o: AC drive status word)
•
Read only
Mappable status word with bit assignment in compliance with
EtherNet/IP™ AC drive prole.
Bit 0 Fault/Trip
Bit 1 Reserved
Bit 2 Running Forward
Bit 3 Running Reverse
Bit 4 Ready
Bit 5 Control from Network
Bit 6 Reference from Network
Bit 7 At Reference
Bit 8 Reserved
Bit 9
Bit 10
Bit 11
Bit 12 Process controller acve
Bit 13 Torque mode acve
Bit 14 Current limit reached
Bit 15 DC braking acve
Conguring the network
Predened process data words
AC Drive Prole
106