11.11 Frequency threshold for "Frequency threshold exceeded" trigger
The "Frequency threshold exceeded [70]" trigger can be used to trigger a certain funcon or
set a digital output when the motor frequency e
xceeds the set frequency threshold set in the
following parameter.
Parameter Name / value range / [default seng] Info
0x4005
(PAR 412)
Frequency threshold
(Freq. threshold
)
0.0 ... [0.0] ... 599.0 Hz
Threshold for the "Frequency threshold exceeded" trigger.
•
The "Frequency threshold exceeded" trigger is TRUE if the current
output frequency > the threshold set.
•
The trigger can be assigned to a funcon or to a digital output.
Flexible I/O conguraon
Frequency threshold for "Frequency threshold exceeded" trigger
209