11.14 Conguraon of digital outputs
11.14.1 Relay
Sengs for the r
elay.
Parameter Name / value range / [default seng] Info
0x2634:001
(PAR 420/001)
Funcon assignment of digital outputs: R
elay
(Digital outputs: Relay funcon)
Assignment of a trigger to the relay.
Trigger = FALSE: X9/NO-COM open and NC-COM closed.
Trigger = TRUE: X9/NO-COM closed and NC-COM open.
Notes:
•
An inversion set in 0x2635:001 (PAR 421/001)is taken into considera-
on here.
0 Not connected No trigger assigned (bit is constantly "0").
1 Constant TRUE Bit is constantly "1".
11 Digital input 1 State of X3/DI1, taking an inversion set in 0x2632:001 (PAR 411/001) into
consideraon.
12 Digital input 2 State of X3/DI2, taking an inversion set in 0x2632:002 (PAR 411/002) into
consideraon.
13 Digital input 3 State of X3/DI3, taking an inversion set in 0x2632:003 (PAR 411/003) into
consideraon.
14 Digital input 4 State of X3/DI4, taking an inversion set in 0x2632:004 (PAR 411/004) into
consideraon.
15 Digital input 5 State of X3/DI5, taking an inversion set in 0x2632:005 (PAR 411/005) into
consideraon.
16 Digital input 6 State of X3/DI6, taking an inversion set in into consideraon.
17 Digital input 7 State of X3/DI7, taking an inversion set in into consideraon.
34 NETWordIN2 - bit 0 State of NetWordIN2/bit 0.
•
Display of NetWordIN2 in 0x4008:002 (PAR 590/002).
•
For controlling the digital outputs via network, NetWordIN2 can be
mapped to a process data input word.
35 NETWordIN2 - bit 1 State of NetWordIN2/bit 1.
36 NETWordIN2 - bit 2 State of NetWordIN2/bit 2.
37 NETWordIN2 - bit 3 State of NetWordIN2/bit 3.
38 NETWordIN2 - bit 4 State of NetWordIN2/bit 4.
39 NETWordIN2 - bit 5 State of NetWordIN2/bit 5.
40 NETWordIN2 - bit 6 State of NetWordIN2/bit 6.
41 NETWordIN2 - bit 7 State of NetWordIN2/bit 7.
42 NETWordIN2 - bit 8 State of NetWordIN2/bit 8.
43 NETWordIN2 - bit 9 State of NetWordIN2/bit 9.
44 NETWordIN2 - bit 10 State of NetWordIN2/bit 10.
45 NETWordIN2 - bit 11 State of NetWordIN2/bit 11.
46 NETWordIN2 - bit 12 State of NetWordIN2/bit 12.
47 NETWordIN2 - bit 13 State of NetWordIN2/bit 13.
48 NETWordIN2 - bit 14 State of NetWordIN2/bit 14.
49 NETWordIN2 - bit 15 State of NetWordIN2/bit 15.
50 Running TRUE if motor is controlled (pulse width modulaon on). Otherwise
FALSE.
51 Ready for
operaon TRUE if operaon is enabled AND no error is acve. Otherwise FALSE.
52 Controller enable TRUE if inverter is not enabled OR stop command is acve and output
frequency = 0.
53 Stop acve TRUE if inverter is not enabled OR Stop command is acve and output
frequency = 0.
FALSE if inverter enabled OR quick stop acve OR fault acve OR output
frequency ≠ 0.
Flexible I/O conguraon
Conguraon of digital outputs
Relay
215