11.1 Control source change-over
The term "control sources" in this connecon refers to the signal sources from which the
inverter receiv
es its start, stop, and reversal commands.
Possible control sources are:
•
Digital inputs
•
Process input data (network)
•
Keypad keys
Details
If exible control is set in 0x2824 (PAR 200), a change-over from one control source to another
can be eected during operaon using corresponding funcons. The inverter not only sup-
ports such a change-over via its digital inputs, but also as a funcon of internal inverter states.
In order to deacvate the digital inputs as control source and use the keypad or network as
control source instead:
•
By means of the "Keypad control" (0x2631:012 (PAR 400/012)) funcon, the keypad can be
acvated as control source. The drive can then be started and stopped via the
and
keypad keys.
•
The "Network enable" (0x2631:037 (PAR 400/037))
funcon serves to acvate the network
control mode. The inverter then responds to the start and stop commands received via net-
work.
Inverter behaviour when the control source is changed
If, during change-over of the control source, a funcon with a level-sensive trigger is acve
(e.g. Quick stop" or "DC braking"), the inverter responds to the new trigger state for the
respecve funcon immediately when the control source is changed over.
If a funcon with an edge-sensive trigger is acve instead (e.g. Forward start (CW)",
"Backward start (CCW)"), this funcon remains acve aer change-over unl another funcon
is acvated by the new control source.
If the keypad key is pressed, this state is saved internally. Restarng the drive
from another control sour
ce therefore requires pressing the
key rst in order
to cancel the stop c
ommand by the keypad again.
Parameter Name / value range / [default seng] Info
0x2631:012
(PAR 400/012)
Funcon assignment: Keypad c
ontrol
(Funcon list: Keypad control)
•
For possible sengs see descripon for
0x2631:001 (PAR 400/001). ^ 188
Assignment of a trigger for the "Keypad control" funcon.
Trigger = TRUE: acvate keypad as control source.
Trigger = FALSE: no acon / deacvate keypad as control source again.
00 Not connected No trigger assigned (trigger is constantly FALSE).
0x2631:037
(PAR 400/037)
Funcon assignment: Network enable
(Funcon list: Network enable)
•
For possible sengs see descripon for
0x2631:001 (PAR 400/001). ^ 188
Assignment of a trigger for the "Network enable" funcon.
Trigger = TRUE: acvate network control mode.
Trigger = FALSE: no acon / deacvate network control mode again.
00 Not connected No trigger assigned (trigger is constantly FALSE).
0x2824
(PAR 200)
Control selecon
(Control source)
Selecon of the type of inverter control.
0 Terminal mode (exible I/O conguraon) This selecon enables a exible assignment of the start, stop, and rotat-
ing direcon commands with digital signal sources (e.g. digital inputs,
process data received via network).
1 Keypad This selecon enables starng and stopping of the inverter exclusively
via the start and stop key of the keypad.
•
Other signal sources for starng the inverter are ignored.
•
This selecon is advisable for an inial funconal test if no external
control sources are connected yet.
Flexible I/O conguraon
Control source change-over
187