10.11 Flying restart funcon
This funcon makes it possible to restart a coasng motor on the y during operaon without
speed feedback. Synchronicity betw
een the inverter and the motor is coordinated so that the
transion to the rotang drive is eected without jerk at the me of connecon.
Precondions
•
The "Flying restart process" funcon is only suit
able for asynchronous motors.
•
The "Flying restart process" funcon is only used if selecon 2 is se
t as starng performance
in 0x2838:001 (PAR 203/001).
Details
The funcon works with a simple motor model requiring knowledge of the motor stator resist-
ance and the rated motor current. The inverter determines synchronicity by idenfying the
synchronous eld frequency. The "Flying restart process" is completed within approx.
0.5 ... 1.5 seconds. The duraon is inuenced by the start frequency 0x2BA1:001
(PAR 718/001). If the eld frequency is not known, a xed start frequency of 10 Hz (or -10 Hz
for systems rotang in the negave direcon) is recommended.
Parameter Name / value range / [default seng] Info
0x2BA1:001
(PAR 718/001)
Flying restart cir
cuit: Current
(Flying restart circuit: Flying restart current)
0 ... [30] ... 100 %
Current that is injected into the motor during the ying restart process
for the idencaon of the speed.
•
Reducing the current causes a reducon of the motor torque during
the ying restart process. A short-me starng acon or reversing of
the motor is prevented with low ying restart currents.
•
If the current is increased, this improves the robustness of the ying
restart funcon.
0x2BA1:002
(PAR 718/002)
Flying restart circuit: Start frequency
(Flying restart circuit: Start frequency)
-599.0 ... [20.0] ... 599.0 Hz
Restart frequency for ying restart process.
0x2BA1:003
(PAR 718/003)
Flying restart circuit: Restart me
(Flying restart circuit: Flying restart me)
1 ... [5911]* ... 60000 ms
•
Default seng depending on the size.
Restart me for ying restart process.
•
The duraon of the ying restart process can be inuenced by the set-
ting of the restart me.
•
A reducon of the restart me causes an accelerated ying restart
process and therefore a reduced ying restart duraon.
0x2BA1:008
(PAR 718/008)
Flying restart circuit: Flying restart frequency
(Flying restart circuit: Flying restart frequency)
•
Read only: x.x Hz
Addional funcons
Flying restart funcon
182