EasyManua.ls Logo

Lenze i510 - Configuration of Analog Outputs; Analog Output 1

Lenze i510
250 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11.15 Conguraon of analog outputs
11.15.1 Analog output 1
Sengs for analog input 1.
Details
The analog output c
an be congured as voltage or curr
ent source.
A seng range can be dened for the source signal selected. Source signals outside the
seng range ar
e eliminated.
Denion of the seng range
The source signal is converted to a percentage value internally on the basis of the seng
range. The reference for the percentage value then is the voltage or current range selected.
Example: with a percentage value of the source signal of 60 % and a conguraon as 0 ... 10 V
voltage source, 6 V are shown at the analog output.
100
0
[%]
Source signal [ ]
Parameter Name Notes
0x2639:003 (PAR 440/003) Min signal value
0x2639:004 (PAR 440/004) Max signal value
Parameter Name / value range / [default seng] Info
0x2639:001
(PAR 440/001)
Analog output 1: Output range
(Analog output 1
: AO1 cong.)
Denion of the output range.
0 Inhibited
1 0 … 10 VDC
2 0 … 5 VDC
3 2 … 10 VDC
4 4 … 20 mA
5 0 … 20 mA
0x2639:002
(PAR 440/002)
Analog output 1: Funcon
(Analog output 1: AO1 funcon)
Selecon of the signal to be shown at analog output 1.
0 Not acve No output signal.
1 Output frequency Current output frequency [0.1 Hz].
2 Frequency setpoint Current frequency setpoint [0.1 Hz].
3 Analog input 1 Input signal from analog input 1 [0.1 %].
4 Analog input 2 Input signal from analog input 2 [0.1 %].
5 Motor current Present motor current [0.1 A].
6 Output power Current output power.
20 NETWordIN3 Mappable NetWordIN3 data word 0x4008:003 (PAR 590/003).
21 NETWordIN4 Mappable NetWordIN4 data word 0x4008:004 (PAR 590/004).
250 Free parameter 1 Free user parameter 1 [16 bits without sign]
251 Free parameter 2 Free user parameter 2 [16 bits with sign]
252 Free parameter 3 Free user parameter 3 [32 bits without sign]
253 Free parameter 4 Free user parameter 4 [32 bits with sign]
0x2639:003
(PAR 440/003)
Analog output 1: Min signal value
(Analog output 1: AO1 funct @ min)
-2147483648 ... [0] ... 2147483647
Denion of the signal value that corresponds to the minimum value at
analog output 1.
Example: conguraon of analog output 1 as a 4 ... 20 mA current loop: