Parameter Name / value range / [default seng] Info
0x2639:004
(PAR 440/004)
Analog output 1: Max signal value
(Analog output 1
: AO1 funct @ max)
-2147483648 ... [1000] ... 2147483647
Denion of the signal value that corresponds to the maximum value at
analog output 1.
Example: conguraon of analog output 1 as a 4 ... 20 mA current loop:
output current 20 mA ≡ 0x2639:004
0x4008:003
(PAR 590/003)
Process input words: NETWordIN3
(NETWordIN stat: NETWordIN3)
0.0 ... [0.0] ... 100.0 %
Mappable data word for oponal control of an analog output via net-
work.
Assignment of the analog outputs:
0x2639:002 (PAR 440/002) = 20: analog output 1 or
= 20: analog output 2
0x4008:004
(PAR 590/004)
Process input words
: NETWordIN4
(NETWordIN stat: NETWordIN4)
0.0 ... [0.0] ... 100.0 %
Mappable data word for oponal control of an analog output via net-
work.
Assignment of the analog outputs:
0x2639:002 (PAR 440/002) = 21: analog output 1 or
= 21: analog output 2