5.3.9 Heatsink Temperature Monitoring
Parameter Name / value range / [default seng] Info
0x2D84:001
(PAR 117/001)
Heatsink tempera
ture monitoring: Actual value
(Heatsink temp.: Heatsink temp.)
•
Read only: x.x °C
Display of the current heatsink temperature.
0x2D84:002 Heatsink temperature monitoring: Warning threshold
50.0 ... [80.0]* ... 100.0 °C
•
Default seng depending on the size.
Warning threshold for temperature monitoring.
•
If the heatsink temperature exceeds the threshold set here, the inver-
ter outputs a warning.
•
The warning is reset with a hysteresis of approx. 5 °C.
•
If the heatsink temperature increases further and exceeds the non-
adjustable error threshold (100 °C), ), the inverter changes to the
"Fault" device status. Further operaon of the inverter is disabled by
controller inhibit.
5.3.10 Diagnoscs mer
The following parame
ters provide some informaon about the use of the inverter.
This includes the following informaon:
•
Operang and power-on me of the inverter/control unit
•
Operang me of the internal fan
•
Number of switching cycles of the mains voltage
•
Number of switching cycles of the relay
•
Number of short-circuits and earth faults that have occurred
•
Display of the number of "Clamp responds too oen" errors that have occurred.
Parameter Name / value range / [default seng] Info
0x2D81:001
(PAR 151/001)
Service life mer: Operang
me
(Timer/counter: Operang me)
•
Read only: x s
Display showing for how long the inverter has been running so far "Oper-
aon enabled" device state).
0x2D81:002
(PAR 151/002)
Display showing for how long the inverter has been switched on so far.
0x2D81:003
(PAR 151/003)
Service life mer: Control unit operang me
(Timer/counter: CU oper. me)
•
Read only: x ns
Display showing how long the control unit of the inverter has been
switched on for so far.
•
This also includes the me within which the control unit has only
been supplied with an external 24 V voltage.
0x2D81:004
(PAR 151/004)
Service life mer: Main Switching Cycles
(Timer/counter: Power cycles)
•
Read only
Display of the number of switching cycles of the mains voltage.
0x2D81:005
(PAR 151/005)
Service life mer: Relay switching cycles
(Timer/counter: Relay cycles)
•
Read only
Display of the number of switching cycles of the relay.
0x2D81:006
(PAR 151/006)
Service life mer: Short-circuit counter
(Timer/counter: Short-circ. counter)
•
Read only
Display of the number of short circuits that have occurred.
0x2D81:007
(PAR 151/007)
Service life mer:
Earth fault counter
(Timer/counter: Earth fault counter)
•
Read only
Display of the number of earth faults that have occurred.
0x2D81:008
(PAR 151/008)
Service life mer: Clamp acve
(Timer/counter: Clamp acve)
•
Read only
Display of the number of "Clamp responds too oen " errors that have
occurred.
•
"Clamp" = short-me inhibit of the inverter in V/f operaon when the
current limit shown in 0x2DDF:002 is reached.
0x2D81:009
(PAR 151/009)
Service life mer: Fan operang me
(Timer/counter: Fan oper. me)
•
Read only: x s
Display showing for how long the internal fan has been running so far.
Diagnoscs and fault eliminaon
Diagnoscs
Heatsink Temperature Monitoring