6.1 Mains voltage
The rated mains voltage set for the inverter has an impact on the operang range of the inver-
ter.
Details
B
y default, the rated mains voltage is set in 0x2540:001 (PAR 208/001) according to the inver-
ter type code.
Check the seng of the rated mains v
oltage in 0x2540:001 (PAR 208/001).
Ensure that it matches the actual mains voltage applied!
The following results from the rated mains voltage set:
•
the error threshold for monitoring the DC-bus v
oltage and
•
the voltage threshold for braking operaon ("brake chopper threshold").
Monitoring of the DC-bus voltage
•
The warning thresholds for monitoring ar
e adjustable.
•
The error thresholds and reset thresholds for monitoring result from the rated mains volt-
age set:
Rated mains volt-
age
Undervoltag
e thresholds Overvoltage thresholds
Warning threshold Error threshold Reset threshold Warning threshold Error threshold Reset threshold
Seng in
0x2540:001
(PAR 208/001)
Seng in
0x2540:002
(PAR 208/002)
Display in
0x2540:003
(PAR 208/003)
Display in
0x2540:004
(PAR 208/004)
Seng
in0x2540:005
(PAR 208/005)
Display in
0x2540:006
(PAR 208/006)
Display in
0x2540:007
(PAR 208/007)
•
If the DC-bus v
olt
ag
e of the in
v
erter falls below the undervoltage error threshold, the "Trou-
ble" response is triggered.
•
If the DC-bus voltage of the inverter exceeds the overvoltage error threshold, the "Fault"
response is triggered.
When the undervoltage or overvoltage monitoring funcon has been acvated,
the drive is not restarted automacally.
Parameter Name / value range / [default seng] Info
0x2540:001
(PAR 208/001)
Mains voltage
: Rated mains voltage
(Mains volt. se.: AC input volt.)
•
Seng can only be changed if controller inhibit is
acve.
Selecon of the mains voltage for actuang the inverter.
0 230 Ve
1 400 Ve
2 480 Ve
0x2540:002
(PAR 208/002)
Mains voltage
: Undervoltage warning threshold
(Mains volt. se.: LU warning level)
0 ... [0]* ... 800 V
•
Default seng depending on the size.
Seng of the warning threshold for monitoring DC bus undervoltage.
•
If the DC bus voltage falls below the threshold set, the inverter out-
puts a warning.
•
The warning is reset with a hysteresis of 10 V.
0x2540:003
(PAR 208/003)
Mains voltage
: Undervoltage error threshold
(Mains volt. se.: LU error level)
•
Read only: x V
•
Default seng depending on the size.
Display of the xed error threshold for monitoring DC bus undervoltage.
•
If the DC-bus voltage falls below the threshold displayed, the "Fault"
response is triggered.
0x2540:004
(PAR 208/004)
Mains voltage
: Undervoltage reset threshold
(Mains volt. se.: LU deleon level)
•
Read only: x V
•
Default seng depending on the size.
Display of the xed reset threshold for monitoring DC bus undervoltage.
Basic seng
Mains voltage
67