Parameter Name / value range / [default seng] Info
0x2541:005
(PAR 706/005)
Brake energy manag
ement: Deceleraon override
me
(Brake management: Del.overr.me)
0.0 ... [2.0] ... 60.0 s
Maximum permissible me for the deceleraon override by means of
the braking method selected in 0x2541:001 (PAR 706/001).
•
If the deceleraon connues for a longer me, the "Overvoltage in
the DC bus" error is tripped.
•
If the DC-bus voltage does not fall below the voltage threshold for
braking operaon shown in 0x2541:002 (PAR 706/002) within this
me, the drive is decelerated further.
•
The me is only reset if the voltage threshold shown in 0x2541:002
(PAR 706/002) is not reached.
0x2540:001
(PAR 208/001)
Mains voltage: Rated mains voltage
(Mains volt. se.: AC input volt.)
•
Seng can only be changed if controller inhibit is
acve.
Selecon of the mains voltage for actuang the inverter.
0 230 Ve
1 400 Ve
2 480 Ve
10.4.1 Stopping the deceleraon ramp funcon generator
The deceleraon ramp funcon generator is stopped for a short me if the voltage threshold
for braking operaon is exceeded.
De
tails
This braking method does not feature any individual parameters.
Addional funcons
Brake energy manag
ement
Stopping the deceleraon ramp funcon generator