10.12 Fault conguraon
Conguraon of the restart behaviour aer a fault.
The fault conguraon has no impact on errors and warnings of the inverter.
Parameter Name / value range / [default seng] Info
0x2826 Time-out for error response
0.0 ... [6.0] ... 100.0 s
This mer is started when a chang
e-over to the "Error response acve"
device state takes place. If no motor standsll is detected aer this me-
out has elapsed, or the motor is sll rotang, a change-over to the
"Error" device state takes place.
Note: If the "coast to stop forced" bit is set when the error has occurred,
an immediate change-over to the "Error" device state takes place.
0x2839:002
(PAR 760/002)
Fault conguraon: Restart delay
(Fault cong.: Ctrl: start-up del)
0.0 ... [3.0] ... 1000.0 s
If a fault occurs, a restart is possible at the earliest aer the me set
here has elapsed.
0x2839:003
(PAR 760/003)
Fault conguraon: Number of rest
art aempts
(Fault cong.: Ctrl: start-up counter)
0 ... [5] ... 255
Number of restart aempts aer a fault.
Note!
With a seng > 1, automac restart of the motor is possible aer a fault
(e.g. device overload)!
0x2839:004
(PAR 760/004)
Fault conguraon: Down-counng me of glit
ch
counter
(Fault cong.: Ctrl:dec.period)
0.1 ... [5.0] ... 3600.0 s
Time of trouble-free operaon aer the expiry of which the fault coun-
ter is decreased by 1.
0x2839:005
(PAR 760/005)
Fault conguraon: Current counter content of glitch
counter
(Fault cong.: Ctrl: curr. counter)
•
Read only
Display of the current fault counter content.
•
The counter content is increased by 1 aer each restart aempt.