Parameter Name / value range / [default seng] Info
0x2000:012
(PAR 190/012)
Power unit - bootloader v
ersion
(PU bootlder ver.)
•
Read only
0x2000:013
(PAR 190/013)
Power unit - bootloader type
(PU bootlder type)
•
Read only
0x2001
(PAR 191)
Device name
(Device name
)
["My Device"]
Any device name (e.g. "Wheel drive") can be set in this object for the
purpose of device idencaon.
5.3.8 Device overload monitoring (i*t)
The inverter calculates the i*t ulisaon in order to prot
ect itself against thermal overload. In
simple terms: a higher current or an overcurrent that connues for a longer me causes a
higher i*t ulisaon.
DANGER!
Uncontrolled motor movements by pulse inhibit.
When the device overload monitoring funcon is
acvated, pulse inhibit is set and the motor
becomes torqueless. A load that is connected to motors without a holding brake may there-
fore cause uncontrolled movements! Without a load, the motor will coast.
▶
Only operate the inverter under permissible load condions.
Details
The device overload monitoring funcon primarily oers protecon to the power secon.
Indirectly
, also other components such as lter chokes, circuit-board conductors, and termi-
nals are protected against overheang. Short-me overload currents followed by recovery
periods (mes of smaller current ulisaon) are permissible. The monitoring funcon during
operaon checks whether these condions are met, taking into consideraon that higher
switching frequencies and lower stator frequencies as well as higher DC voltages cause a
greater device ulisaon.
•
If the device ulisaon exceeds the warning threshold set in 0x2D40:002 (Lenze seng:
95 %), the inverter outputs a warning. The user can ulise this status as a trigger to acvate
specic funcons.
•
If the device ulisaon exceeds the xed error threshold 100 %, the inverter changes to the
"Trouble" device state. Further operaon of the inverter is prevented by controller inhibit.
Controlled standsll can only be executed by the use of a mechanical brake.
Device overload monitoring enables operaon of the inverter under the following load condi-
ons:
•
Connuous current load with up to 100 % rated current.
•
3-minute cycle: 150 % rated current for 60 s, recovery phase 120 s with 75 % rated current.
•
15-second cycle: 200 % rated current for 3 s, recovery phase 12 s with 75 % rated current.
Parameter Name / value range / [default seng] Info
0x2D40:002 Device ulisaon (i*t): Warning threshold
0 ... [95] ... 101 %
If the device ulisaon exceeds the threshold set, the inverter outputs a
warning.
•
With the seng 0 % or 101 %, the warning is
deacvated.
0x2D40:004
(PAR 135/004)
Device ulisaon (i*t): Actual ulisaon
(Device ulisaon: Ixt ulisaon)
•
Read only: x %
Display of the current device ulisaon.
0x2D40:005
(PAR 135/005)
Device ulisaon (i*t): Err
or response
(Device ulisaon: Error response)
Selecon of the response to be executed when the device overload
monitoring funcon is triggered.
2 Trouble
3 Error
0x2DDF:001 Axis informaon: Rated current
•
Read only: x.xx A
•
Def
ault seng depending on the size.
Diagnoscs and fault eliminaon
Diagnoscs
Device overload monitoring (i*t)
61