7.4 Opmisaon of the control loops
The following speed controller, Imax controller and current controller parameters are calcula-
ted and set automacally and in the cour
se of the automac calibraon of the motor.
Details
•
The calibraon process can be carried out in "energised" or in "non-energised" mode.
•
The calibraon process takes all controllers into consideraon at the same me; it is not
possible to control the speed controller Imax controller, and current controller separately.
•
Without carrying out the calibraon, standard values are preset according to the voltage
and power of the inverter.
•
When the automac calibraon has been carried out, further adaptaon is neither required
nor recommended for typical applicaons.
If these parameters have to be adapted, this has to be done very carefully. An
incorrect seng may hav
e a negave impact on the control system.
7.4.1 Speed controller
Parameter Name / value range / [default seng] Info
0x2900:001
(PAR 332/001)
Speed controller par
ameters: Gain
(Speed controller: Speed contr.: gain)
0.00000 ... [0.00193]* ... 20000.00000 Nm/rpm
•
Default seng depending on the size.
Gain factor Vp of the speed controller.
0x2900:002
(PAR 332/002)
Speed controller parameters: Reset me
(Speed controller: Speed contr.: me)
1.0 ... [80.0]* ... 6000.0 ms
•
Default seng depending on the size.
Reset me Ti of the speed controller.
0x2904 Filter me
0.0 ... [2.0] ... 50.0 ms
Filter me for the actual speed value.
7.4.2 Imax controller
Parameter Name / value range / [default seng] Info
0x2B08:001
(PAR 333/001)
V/f Imax con
troller: Gain
(V/f Imax controller: Imax ctrller: gain)
0.000 ... [0.284]* ... 1000.000 Hz/A
•
Default seng depending on the size.
Gain factor Vp of the Imax controller.
0x2B08:002
(PAR 333/002)
V/f Imax controller: Reset me
(V/f Imax controller: Imax ctrller: me)
1.0 ... [2.3]* ... 2000.0 ms
•
Default seng depending on the size.
Reset me Ti of the Imax controller.
7.4.3 Current controller
Parameter Name / value range / [default seng] Info
0x2942:001
(PAR 334/001)
Current con
troller parameters: Gain
(Current controller: I-contr.: gain)
0.00 ... [42.55]* ... 750.00 V/A
•
Default seng depending on the size.
Gain factor Vp of the current controller.
0x2942:002
(PAR 334/002)
Current controller parameters: Reset me
(Current controller: I-contr.: me)
0.01 ... [4.50]* ... 2000.00 ms
•
Default seng depending on the size.
Reset me Ti of the current controller.
Motor control
Opmisaon of the control loops
Speed controller
89