9.2.2 Process controller rinse funcon
This funcon accelerates the drive in sleep mode to a dened speed at regular intervals. The
rinsing of a pump that has been in an inacve stat
e for a longer period is a typical applicaon.
Parameter Name / value range / [default seng] Info
0x4024:001
(PAR 615/001)
Automac rinsing: Rinsing in idle sta
te
(Set auto-rinse: Auto-rinse mode)
1 = acvate automac rinsing in idle state.
0 Inhibited
1 Enabled
0x4024:002
(PAR 615/002)
Automac rinsing: Time period between rinsing
processes
(Set auto-rinse: Auto-rinse del.)
0.0 ... [30.0] ... 6000.0 min
Time interval between two rinsing processes.
0x4024:003
(PAR 615/003)
Automac rinsing: Speed
(Set auto-rinse: Auto-rinse speed)
-599.0 ... [0.0] ... 599.0 Hz
Speed setpoint for rinse funcon.
0x4024:004
(PAR 615/004)
Automac rinsing: Duraon of rinsing process
(Set auto-rinse: Auto-rinse me)
0.0 ... [0.0] ... 6000.0 s
Duraon of a rinsing process.
Conguring the process controller
Process controller - idle s
tate and rinse funcon
Process controller rinse funcon
143