Sengs for digital output 1.
Parameter Name / value range / [default seng] Info
0x2634:002
(PAR 420/002)
Funcon assignment of digital outputs: Digit
al output
1
(Digital outputs: DO1 funcon)
For possible sengs see descripon for
0x2634:001 (PAR 420/001). ^ 215
Assignment of a trigger to digital output 1.
Trigger = FALSE: X3/DO1 set to LOW level.
Trigger = TRUE: X3/DO1 set to HIGH level.
Notes:
An inversion set in 0x2635:002 (PAR 421/002) is taken into considera-
on here.
115 Release holding brake TRUE if the holding brake is released (or should be released). Otherwise
FALSE.
0x2635:002
(PAR 421/002)
Inversion of digital outputs: Digital output 1
(DO inversion: DO1 inversion)
Inversion of digital output 1
0 Not inverted
1 Inverted
0x4016:003 Digital output 1: Cutout delay
0.000 ... [0.020] ... 65.535 s
Switch-o delay for digital output 1.
0x4016:004 Digital output 1: Switch-on delay
0.000 ... [0.020] ... 65.535 s
Switch-on delay for digital output 1.
0x4016:005 Digital output 1: Terminal state
Read only
Display of the logic state of output terminal X3/DO1.
0 FALSE
1 TRUE
0x4016:006 Digital output 1: Trigger signal state
Read only
Display of the logic state of the trigger signal for digital output 1 (without
taking a ON/OFF delay set and inversion into consideraon).
0 FALSE
1 TRUE
11.14.3 NETWordOUT1 status word
Assignment of digital triggers to bit 0 ... bit 15 of the NETWordOUT1 status word.
Parameter Name / value range / [default seng] Info
0x2634:010
(PAR 420/010)
Funcon assignment of digital outputs:
NETW
ordOUT1 - bit 0
(Digital outputs: NETWordOUT1.00)
For possible sengs see descripon for
0x2634:001 (PAR 420/001). ^ 215
Assignment of a trigger to bit 0 of NETWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
51 Ready for operaon TRUE if operaon is enabled AND no error is acve. Otherwise FALSE.
0x2634:011
(PAR 420/011)
Funcon assignment of digital outputs:
NETWordOUT1 - bit 1
(Digital outputs: NETWordOUT1.01)
For possible sengs see descripon for
0x2634:001 (PAR 420/001). ^ 215
Assignment of a trigger to bit 1 of NETWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
69 Reversal acve TRUE if reversal is acve. Otherwise FALSE.
Selecon of the trigger for the "Reversal" funcon in 0x2631:013
(PAR 400/013).
0x2634:012
(PAR 420/012)
Funcon assignment of digital outputs:
NETWordOUT1 - bit 2
(Digital outputs: NETWordOUT1.02)
For possible sengs see descripon for
0x2634:001 (PAR 420/001). ^ 215
Assignment of a trigger to bit 2 of NETWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
50 Running TRUE if motor is controlled (pulse width modulaon on). Otherwise
FALSE.
0x2634:013
(PAR 420/013)
Funcon assignment of digital outputs:
NETWordOUT1 - bit 3
(Digital outputs: NETWordOUT1.03)
For possible sengs see descripon for
0x2634:001 (PAR 420/001). ^ 215
Assignment of a trigger to bit 3 of NETWordOUT1.
Trigger = FALSE: bit set to 0.
Trigger = TRUE: bit set to 1.
56 Error acve TRUE if error is acve. Otherwise FALSE.
Flexible I/O conguraon
Conguraon of digital outputs
Digital output 1
218