10.1.2 Saving/loading the parameter sengs
If parameter sengs of the inverter are changed, these changes at rst are only made in the
RAM memory of the inverter
. In order to save the parameter sengs with mains failure pro-
tecon, the inverter is provided with a pluggable memory module and corresponding device
commands.
Details
The memory module is provided with two memories, the user memory and the OEM memory.
•
The keypad can be used to sa
ve changed parameter sengs in the user memory by clicking
the ke
ypad Enter key > 3 s.
•
Parameter sengs carried out with »EASY Starter« or via network must be explicitly saved
in the user memory by means of the "Save data in the user memory" device command, so
that the changes carried out are not lost when the mains of the inverter are switched.
OEM memory
The OEM memory is provided for the storage of customised parameter sengs by the OEM/
mechanical engineer. If the user carries out parameter sengs with the keypad, they are
always saved in the user memory if the keypad Enter key is clicked > 3 s. The OEM memory
remains unaected by these changes.
•
With the "Load data from the OEM memory
" device command, the parameter sengs pre-
congured by the OEM/mechanical engineer can be reloaded to the RAM memory of the
inverter anyme, if requir
ed.
•
Parameter sengs can only be stored in the OEM memory with »EASY Starter« or via net-
work. This explicitly requires execuon of the "Save data in the OEM memory" device com-
mand. At the same me, the parameter sengs are stored in the user memory.
Response aer inial switch-on of the inverter
Aer switch-on, the inverter rst tries to load the parameter sengs stored in the user mem-
ory. If the user memory is empty or damaged, an error message is output and the user must
intervene:
•
Opon 1 = user memory empty: → Lenze seng is loaded automacally → data are saved
automacally in the user memory of the memory module.
•
Opon 2 = user memory damaged: → error message → Lenze seng is loaded manually →
data are saved manually in the user memory of the memory module.
•
Opon 3 = OEM memory empty/damaged: → error message → data are loaded manually
from the user memory of the memory module.
Parameter Name / value range / [default seng] Info
0x2022:003
(PAR 700/003)
Device commands: Sav
e data in the user memory
(Device commands: Save user data)
1 = save current parameter sengs in the main memory of the memory
module with mains failure protecon.
•
It may take some seconds t
o execute the task. When the task has
been executed successfully, the value 0 is shown.
•
Do not switch o the supply voltage during the saving process and do
not unplug the memory module from the invert
er!
•
When the inverter is switched on, all parameters are automacally
loaded from the main memory of the memory module to the RAM
memory of the inverter.
0 O / ready Only status feedback.
1 On / start Execute device command.
2 In progress Only status feedback.
3 Acon cancelled
4 No access
5 No access (controller inhibit)
Addional funcons
Device Commands
Saving/loading the par
ameter sengs
146