EasyManua.ls Logo

Lenze i510 - Fieldbus Communication

Lenze i510
250 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Name / value range / [default seng] Info
0x2D45:002
(PAR 310/002)
Motor phase failure detecon: Curr
ent threshold
(Motor Ø failure: Ø error current)
1.0 ... [5.0] ... 10.0 %
Current threshold for the acvaon of the motor phase failure detecon
funcon.
100 % ≡ Maximum current 0x2DDF:002
Backgr
ound: in order to be able to reliably detect the failure of a
motor phase, rst a certain must ow for the current sensor system.
The detecon funcon is theref
ore only acvated if the actual value
of the motor current has exceeded the current threshold set here.
Display of actual value for the motor current in 0x6078 (PAR 103).
0x2D45:003
(PAR 310/003)
Motor phase failure detecon: Voltage threshold
(Motor Ø failure: Ø error volt.)
0.0 ... [10.0] ... 100.0 V
Voltage threshold for the monitoring of several motor phases.
The V/f characterisc control enables the detecon of several failed
motor phases during operaon.
Monitoring with regard t
o the failure of several motor phases is acve
if a response that is not "0: No response" is set in 0x2D45:001
(PAR 310/001) and if the motor voltag
e exceeds the voltage threshold
set here.
The monitoring funcon is triggered if the level of the motor current
is lower than the device-dependent threshold for longer than 20 ms.
The monitoring funcon for the failure of several motor phases can
be deacvated if the value "100.0 V" is set here.
7.7.5 Motor speed monitoring
Use this funcon to monitor the motor speed during running operaon.
Precondions
In order to r
ecord the current motor speed, the drive must run and the motor must rotate.
Parameter Name / value range / [default seng] Info
0x2D44:001
(PAR 350/001)
Overspeed monitoring
: Threshold
(Overspeed monit.: Overspeed: threshold)
50 ... [8000] ... 50000 rpm
Warning/error threshold for motor speed monitoring.
If the motor speed reaches the threshold set, the response selected in
0x2D44:002 (PAR 350/002) is eected.
0x2D44:002
(PAR 350/002)
Overspeed monitoring: Response
(Overspeed monit.: Overspeed: response)
For possible sengs see descripon for
0x2D45:001 (PAR 310/001). ^ 94
Selecon of the response to the triggering of motor speed monitoring.
3 Error
Motor control
Motor protecon
Motor speed monitoring
95
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.actechdrives.com - Email: info@actechdrives.com

Table of Contents

Other manuals for Lenze i510