Parameter Name / value range / [default seng] Info
0x2022:010
(PAR 700/010)
Device commands: Load parame
ter set 4
(Device commands: Load par. set 4)
1 = load value set 4 of the "Parameter change-over" funcon.
•
The parameters specied in 0x4041/1...32 ar
e set to the values set in
0x4045/1...32.
•
Aer successful execuon, the value 0 is shown.
4Parameter chang
e-over ^ 167
0 O / ready Only status feedback.
1 On / start Execute device command.
2 In progress Only status feedback.
3 Acon cancelled
4 No access
5 No access (controller inhibit)
10.1.4 Inialising the network interface
Changed communicaon sengs (e.g. baud ra
te or node address) only become eecve
when the network interface has been inialised. This either requires switching the inverter o
and on again or execung the "Reset network node" device command.
Parameter Name / value range / [default seng] Info
0x2022:016
(PAR 700/016)
Device commands: Rese
t network node
(Device commands: Reset netw. node)
0 ... [0] ... 1
•
Seng can only be changed if controller inhibit is
acve.
1 = inialise network interface.
•
Required when the baud rate, node address, or ideners are
changed.
•
Aer successful execuon, the value 0 is shown.
0x2022:027
(PAR 700/027)
Device commands: Accept new inverter hardware
(Device commands: Accept new HW)
0 ... [0] ... 1
•
Seng can only be changed if controller inhibit is
acve.
1 = inialise parameters for a new network opon.
10.1.5 Updang the memory module data format
If the memory module contains valid parameter data of a previous rmware version they can
be converted t
o a format matching the current rmware version of the inverter by means of
the "Updang the memory module data format" device command.
When this device command has been executed, the data in the memory module
are no longer compable with pre
vious rmware versions!
Details
•
The inverter also work
s with parameter sengs of a previous rmware version. However, it
is only possible to make changes to the par
ameter sengs if the parameter sengs in the
memory module match the rmware version of the inverter.
•
The keypad shows the "PS02 error" message if the parameter data in the memory module
deviate from the rmware version of the inverter.
Parameter Name / value range / [default seng] Info
0x2022:026
(PAR 700/026)
Device commands: Updang the memor
y module
data format
(Device commands: Compile EPM)
0 ... [0] ... 1
•
Seng can only be changed if controller inhibit is
acve.
1 = convert parameter data in the memory module to a format matching
the current rmware version of the inverter.
Addional funcons
Device Commands
Inialising the network in
terface
149