6.6 Quick stop
Parameter Name / value range / [default seng] Info
0x291C
(PAR 225)
Quick stop deceleraon me
(QSP dec.
me)
0.0 ... [1.0] ... 3600.0 s
If the "Quick stop" funcon is acvated, the motor is brought to a stand-
sll within the deceleraon me set here.
The deceleraon me set refers to the deceleraon from the maximum
frequency set to standsll. In the case of a lower actual frequency, the
actual deceleraon me is reduced accordingly.
0x2631:003
(PAR 400/003)
Funcon assignment: Quick stop
(Funcon list: Quick stop)
Seng can only be changed if controller inhibit is
acve.
For possible sengs see descripon for
0x2631:001 (PAR 400/001). ^ 188
Assignment of a trigger for the "Quick stop" funcon.
Trigger = TRUE: "Quick stop" funcon acvated.
Trigger = FALSE: no acon / deacvate funcon again.
Notes:
The "Quick stop" funcon brings the motor to a standsll within the
deceleraon me set in 0x291C (PAR 225).
The "Quick stop" funcon has a higher priority than the "Start enable"
funcon.
00 Not connected No trigger assigned (trigger is constantly FALSE).