1.Use the key in the operang mode to naviga
te to the
parameterisaon mode one level below.
You are now in the group level. All parameters of the
inverter are divided into dierent groups according to
their funcon.
Group 0 contains the "Favorites".
Note: By using the
key you can navigate one level
upwards again anyme.
2.Use the key to navigate to one level below.
You are now in the parameter le
vel of the group selec-
ted.
3.Use the
and navigaon keys to select the desired
paramet
er.
4.Use the
key to navigate to one level below.
You are now in the eding mode.
5.Set the desir
ed value using the
and navigaon
keys.
6.Use the key to accept the changed seng.
The eding mode is exited.
Note: B
y using the
key you can exit the eding mode
without accepng the new seng (abort).
10.7.2 Fav
orites parameter list (default seng)
In the default seng, the most common parameters for the soluon of typical applicaons
are dened as "Favorites":
No. Display Name Default seng Seng range Info
1 P100.00 Actual frequency x.x Hz - (Read only) 0x2DDD (PAR 100)
2 P103.00 Motor curr
ent % x.x % - (Read only) 0x6078 (PAR 103)
3 P106.00 Motor voltage x VAC - (Read only) 0x2D89 (PAR 106)
4 P150.00 Acve error - - (Read only) 0x603F (PAR 150)
5 P200.00 Control source Terminal mode [0] Selecon list 0x2824 (PAR 200)
6 P201.01 Frequency setp. Analog input 1 [2] Selecon list 0x2860:001 (PAR 201/001)
7 P203.01 Start method Normal [0] Selecon list 0x2838:001 (PAR 203/001)
8 P203.03 Stop method Standard Ramp [1] Selecon list 0x2838:003 (PAR 203/003)
9 P208.01 AC input volt. 230 Ve [0] Selecon list 0x2540:001 (PAR 208/001)
10 P210.00 Min. frequency 0.0 Hz 0.0 ... 599.0 Hz 0x2915 (PAR 210)
11 P211.00 Max. frequency 50.0 Hz 0.0 ... 599.0 Hz 0x2916 (PAR 211)
12 P220.00 Acceleraon me 1 5.0 s 0.0 ... 3600.0 s 0x2917 (PAR 220)
13 P221.00 Deceleraon me 1 5.0 s 0.0 ... 3600.0 s 0x2918 (PAR 221)
14 P300.00 Motor ctrl mode VFC open loop [6] Selecon list 0x2C00 (PAR 300)
15 P302.00 V/f curve Linear [0] Selecon list 0x2B00 (PAR 302)
16 P303.01 Base voltage 230 V 0 ... 5000 V 0x2B01:001 (PAR 303/001)
17 P303.02 Base frequency 50 Hz 0 ... 599 Hz 0x2B01:002 (PAR 303/002)
Addional funcons
Favorit
es
Accessing the "Favorites" with the keypad
162