Hard Limit
These alarms are triggered by the homing sensors. If a mechanical fault occurs that causes the axis to
trigger a hard limit the Hard Limit alarm will be displayed.
To clear the alarm find and clear the issue that caused the Hard limit alarm and Home the machine to clear
the alarm.
Probing alarm
A Probing alarm occurs during a probing cycle where Masso does not receive a signal from the probing
sensor within the specified distance.
You will also get a probing alarm if the probe is already in the active state when a probing cycle is started.
To clear issue a new probing command with a valid distance ensuring the probe is not already in an active
state.
Tool Error Alarm
This occurs if you try and load a tool not supported by Masso. EG the tool number is greater that 99 0n the
G3 or Greater that 31 on the G2
Drive Alarm
When a Stepper or Servo drive goes into an alarm condition the Drive can signal Masso which will put the
system into Feedhold and stop the spindle.
The Drive alarm indication will be displayed on the screen. you drive must be capable of providing the
required signal and they be connected to Masso.
To clear the alarm first clear the fault with the drive and home the machine to clear Alarm indication on
Masso.
Lubricant Low alarm
If you have a lubricant vessel that has an alarm output you can connect it to Masso and a Lubrication alarm
will display on Masso.
Top up your lubricant vessel and the alarm will automatically clear.