8.2 Error Codes and System Alarm List
317
Too high frequency of data collection.
Review conditions.
Data of an object, to which [Collect data only when trigger conditions are satisfied] is
set, are collected too frequently, or the number of objects has exceeded the number
of objects collectable simultaneously.
• Set a longer cycle for trigger occurrence to each object.
• Make the settings so that 257 or more display triggers of objects, to which [Collect
data only when trigger conditions are satisfied] is set, do not occur simultaneously.
320
Specified object does not exist or out
of range.
The part file does not exist.
Create the part file and download to GOT.
322
Dedicated device is out of range.
Confirm device range.
The monitored device No. is out of the permissible area of the targeted PLC CPU.
Set the device within the range that can be monitored by the monitored PLC CPU
and parameter settings.
326
Label data types do not match.
Confirm the label setting.
• The data type of the device assigned to the label is incorrect.
For the available data type of global labels, refer to the following.
➠ GT Designer3 (GOT2000) Help
• The data type of object devices or others and that of labels set on the PLC side are
inconsistent.
Correct the data type of the objects or others according to that of the labels set on
the PLC side.
• A constant value is set for the label.
In the object setting, do not use the label in which a constant value is set.
• A 64-bit type device is assigned to the label.
Do not use a 64-bit type label in the device setting.
327
Label names have not been
resolved. Resolve label names
again.
Check the connection status of the PLC and execute the label name resolution again.
328
Label setting error. Confirm the label
setting.
• The label is set for the PLC which does not support labels.
Correct the network No. and station number.
• The label name specified in the project data does not exist on the PLC side.
Check if the label name specified in the project data exists on the PLC side.
• The GOT access the label inaccessible from external devices.
Enable the access from external devices in the label setting on the PLC side.
• When a global label of structure has members to which devices are manually
assigned, the GOT fails to perform the label name resolution.
Perform operations so that the devices are automatically assigned to the
members, or directly set the manually assigned devices as monitor devices.
329
Station No. switching does not
support labels.
Do not perform the station No. switching to the station using labels.
330
Insufficient memory media capacity.
Confirm M-card capacity.
Available memory of the memory card is insufficient.
Confirm the available memory of the memory card.
The available memory can be confirmed by system information screen, which is
described in GT Designer3 (GOT2000) Help.
331
Memory card not installed or M-
CARD switched OFF
The memory card is not installed in the drive, or the SD card cover is opened.
• Install the memory card in the specified drive.
• Close the SD card cover to make the SD card accessable.
332 Memory media is not formatted.
Memory card (build-in SD card) is not formatted or formatted incorrectly.
Format the memory card.
333
Unable to overwrite. Memory card is
write-protected.
Memory card (build-in SD card) is write-protected.
Cancel the write-protection of memory card.
334
Memory media error. Replace
memory media.
Memory card (build-in SD card) is faulty.
Replace the memory card.
336
The target file size is too large to be
accessed.
• Check if the size of the file that the GOT attempts to access is larger than 2 GB.
• Check that the size of the image file is 300 KB or smaller.
337
File output failed. Confirm output file
path.
Either of the following folder or file with the name same as the file to be created exists
in the storage destination SD card or USB memory.
• Folder storing data
• Write-protect file
Delete the above folder or file, or change the name of the file to be created.
338
Modem is not connected correctly or
the power is not turned on.
There is no response to the initializing command because the modem is not
connected correctly or the power is not turned on.
• Confirm the modem connection.
• Turn on the power of the modem.
339
Failed to initialize the modem. Check
initialization command.
An error is returned from the modem because the initializing command is invalid.
• Confirm the initializing command of the modem.
Error
code
Error message Action
Channel
No. storage