5 - 19
5 EtherCAT Communications
AC Servomotors/Servo Drives 1S-series with Built-in EtherCAT® Communications User’s Manual (I586)
5-8 Sysmac Device Features
5
The Slave Information Interface (SII) contains EtherCAT slave configuration information that is written
to the non-volatile memory of an EtherCAT slave.
Sysmac Device EtherCAT slaves check the SII information from the slave side.
If one of these slaves finds that SII information with which it cannot operate was written, it generates an
SII Verification Error (Error No. 88.03) or ESC Initialization Error (Error No. 88.01). If this error is not
cleared after the power cycle, contact your OMRON sales representative.
Precautions for Correct Use
Do not use non-OMRON configuration tools to edit the SII information.
SII Data Check

Table of Contents

Other manuals for Omron R88D-1SN ECT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron R88D-1SN ECT Series and is the answer not in the manual?

Omron R88D-1SN ECT Series Specifications

General IconGeneral
FeedbackIncremental encoder, Absolute encoder
Position ControlYes
Speed ControlYes
Torque ControlYes
Communication InterfaceEtherCAT
Power Supply Voltage200 to 240 VAC
Output Power0.1 to 1.5 kW
Input Voltage Range170 to 264 VAC
Control MethodSine-wave PWM control
Main Circuit Power Supply200-240 VAC
Applicable Motor Capacity0.1 to 1.5 kW
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheating, Encoder Error
Ambient Operating Temperature0 to 55°C
Vibration Resistance4.9 m/s² (10 to 55 Hz)
Shock Resistance98 m/s2
WeightVaries by model