EasyManua.ls Logo

Sel SEL-787 - Page 522

Sel SEL-787
612 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
F.12
SEL-787 Relay Instruction Manual Date Code 20150130
IEC 61850 Communications
IEC 61850 Configuration
Some measured values are reported to IEC 61850 only when the value
changes beyond a defined dead-band value.
ACSELERATOR Architect allows a
dead band to be changed during the CID file configuration. Check and set the
dead-band values for your particular application when configuring the CID
file for a device.
ACSELERATOR Architect has the capability to read other manufacturers’ ICD
and CID files, enabling the user to map the data seamlessly into SEL IED
logic. See the
ACSELERATOR Architect online help for more information.
SEL ICD File Versions
ACSELERATOR Architect generates CID files from ICD files so the ICD file
version
ACSELERATOR Architect uses also determines the CID file version
generated. Details about the different SEL-787 ICD files can be found in
Table A.5.

Table of Contents