F.32
SEL-787 Relay Instruction Manual Date Code 20150130
IEC 61850 Communications
Protocol Implementation Conformance Statement
Table F.20 lists specific settings for the MMS parameter Conformance
Building Block (CBB).
The following Variable Access Conformance Statements (Table F.21 through
Table F.28) are listed in the order specified in the IEC 61850 standard, Part 8-
1. Generally, only those services whose implementation is not mandatory are
shown. Refer to the IEC 61850 standard Part 8-1 for more information.
Table F.20 MMS Para m e ter CBB
MMS Parameter CBB Client-CR Supported Server-CR Supported
STR1 Y
STR2 Y
VNAM Y
VADR Y
VA LT Y
TPY Y
VLIS Y
CEI
Table F.21 Alternate Access Selection Conformance Statement
Alternate Access Selection Client-CR Supported Server-CR Supported
accessSelection Y
component Y
index
indexRange
allElements
alternateAccess Y
selectAccess Y
component Y
index
indexRange
allElements
Table F.22 VariableAccessSpecification Conformance Statement
VariableAccessSpecification Client-CR Supported Server-CR Supported
listOfVariable
Y
variableSpecification Y
alternateAccess Y
variableListName
Y

Table of Contents