Configuring the fieldbus
7.7 Communication over CANopen
Inverter with CU230P-2 Control Units
Operating Instructions, 11/2013, FW V4.6.6, A5E02430659B AG
203
Interconnecting process data via a free PDO mapping
Procedure
To interconnect process data, proceed as follows:
1. Define process data,
examples:
Send actual current value (r0068) from the inverter to the controller (TPDO - Transmit
Process Data Object)
Send additional speed setpoint from the controller to the inverter (RPDO - Receive
Process Data Object) and write in p1075
2. Specify objects for transmission of the process data
TPDO1 for the actual current value
RPDO1 for additional speed setpoint
3. Set communication parameters for RPDO and TPDO
Define the communication parameters for RPDO, see RPDO communication
parameters (Page 209)
Define the communication parameters for TPDO, see TPDO communication
parameters (Page 212)
4. Select the OD index for the mapping parameters:
Mapping parameters for RPDO, see RPDO mapping parameters (Page 210)
Mapping parameters for TPDO, see TPDO mapping parameters (Page 214)
5. Write OV index into the SINAMICS mapping parameters
p8710 … p8717 for RPDO
p8730 … p8737 for TPDO
You will find the OD index in the free objects (Page 216) or in the objects of the CiA
402 drive profile (Page 207)
Note
Requirement for changing the OD indexes of the SINAMICS mapping parameters
To allow you to change the values of the mapping parameters, you must set the COB ID
of
the corresponding parameter to invalid. Add the value 80000000 hex to the COB ID. If
you have changed the mapping parameter, you must reset the COB ID to the valid value.
You have interconnected the process data.