Page #147 background image
10-11
Table 10-3. Crash Codes (continued)
Code Meaning Cause Corrective Action
16 Bad Card State The state index for a card was invalid for the cards type Reload BIN File
17 Failed Restoring
SMPL
Not Used. Erroneous call to the crash handler *
18 Unable to Restore
CFIG
The flash chip copy to RAM function returned an error Replace Hardware
19 Task 1 Stopped Supervisor task watchdog timer has expired. *
1A Task 2 Stopped Front panel task watchdog timer has expired. Reload CFIG. Check
versions of panel and tools.
1B Task 3 Stopped System operation task watchdog timer has expired Reload CFIG. Check
versions of panel and tools.
1C Task 4 Stopped Communication task watchdog timer has expired Reload CFIG. Check
versions of panel and tools.
1D Task5 Stopped Serial port task watchdog timer has expired. Reload CFIG. Check
versions of panel and tools.
1E Task 6 Stopped Not used. Erroneous call to the crash handler. *
1F Task 7 Stopped Not used. Erroneous call to the crash handler. *
20 Common Overrun Execution across the common code area boundary was
detected.
Reload BIN file.
21 Bank 0 Overrun Execution across the code bank 0 area boundary was
detected.
Reload BIN file.
22 Bank 1 Overrun Execution across the code bank 1 area boundary was
detected.
Reload BIN file.
23 Bank 2 Overrun Execution across the code bank 2 area boundary was
detected.
Reload BIN file.
24 Bank 3 Overrun Execution across the code bank 3 area boundary was
detected.
Reload BIN file.
25 Bank 4 Overrun Execution across the code bank 4 area boundary was
detected.
Reload BIN file.
26 Bank 5 Overrun Execution across the code bank 5 area boundary was
detected.
Reload BIN file.
27 Bank 6 Overrun Execution across the code bank 6 area boundary was
detected.
Reload BIN file.
28 Bank 7 Overrun Execution across the code bank 7 area boundary was
detected.
Reload BIN file.
29 Bank 8 Overrun Execution across the code bank 8 area boundary was
detected.
Reload BIN file.
2A Bank 9 Overrun Execution across the code bank 9 area boundary was
detected.
Reload BIN file.
2B Bank 10 Overrun Execution across the code bank 10 area boundary was
detected.
Reload BIN file.
2C Bank 11 Overrun Not used. Erroneous call to the crash handler. *
2D Bank 12Overrun Not used. Erroneous call to the crash handler. *
2E Bank 13 Overrun Not used. Erroneous call to the crash handler. *
2F Bank 14 Overrun Not used. Erroneous call to the crash handler. *
30 Bank 15 Overrun Not used. Erroneous call to the crash handler. *
31 Bank 16 Overrun Not used. Erroneous call to the crash handler. *
Continued on next page
Crash Codes, Continued
Dia
g
nostics/Troubleshootin
g
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Simplex 4010

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4010 and is the answer not in the manual?

Simplex 4010 Specifications

General IconGeneral
DisplayLCD
Power Supply120/240 VAC, 50/60 Hz
ManufacturerSimplex
Model4010
Battery Backup24 VDC
NAC Outputs4
Max Detectors250
Max Modules250
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity RangeUp to 93% RH, non-condensing