10-12
Table 10-3. Crash Codes (continued)
Code Meaning Cause Corrective Action
32 Network Buffer
Error
The network card local port buffer handler lost a buffer Reload Job / Check
versions of tools and panel
/ reload BIN File
33 Bad Mapnet Packet The mapnet card received a packet that failed its
consistency check.
Reload Job / Check
versions of tools and panel
/ reload BIN File
34 Bad Parameter An LCD function was passed an illegal or impossible
value.
Reload Job / Check
versions of tools and panel
/ reload BIN File
35 Out of Memory The LCD processing failed to allocate a global memory
buffer
Reload Job / Check
versions of tools and panel
/ reload BIN File
36 CFIG Consistency The RAM CFIG area failed its CRC calculation during a
background check.
Reload Job / Check
versions of tools and panel
/ reload BIN File
37 Bad String Length The system called the string format function (sprintf) with
a format string greater than 59 characters.
Reload Job / Check
versions of tools and panel
/ reload BIN File
38 Illegal Crash Code Erroneous call to the crash handler. *
* denotes a code that should never appear.
Crash Codes, Continued
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Simplex 4010

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4010 and is the answer not in the manual?

Simplex 4010 Specifications

General IconGeneral
DisplayLCD
Power Supply120/240 VAC, 50/60 Hz
ManufacturerSimplex
Model4010
Battery Backup24 VDC
NAC Outputs4
Max Detectors250
Max Modules250
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity RangeUp to 93% RH, non-condensing

Related product manuals